Specification for SiteI/O 10/0 
 
 
 
 
DESCRIPTION:  
The SiteI/O 10/0 is part of the SiteI/O-Line, which allows a complete SiteScan 
monitoring/control system to be built a piece at a time.  It is a 32 bit microprocessor-based device 
designed to monitor up to ten analog, digital, and/or dry contact type signals.  Individual hardware 
jumpers set signal-type selections.  Screw terminal blocks are provided to terminate power, 
communication, and input signal wiring.  
 
DIMENSIONS: 
Module: 
7.5” H x 11.3125” W x 2.75” D 
 
 
19.05 cm H x 28.73 cm W x 7 cm D 
 
 
Enclosure:  
20" H x 18" W x 2.87" D 
 
(Painted Steel) 
508mm x 457.2mm x 72.89mm 
 
 
See Enclosure Diagrams for mounting options
 
POWER: 24VAC 
± 10%, 50-60 Hz., 20 VA power consumption 
 
(120/24VAC 40VA Transformer available) 
 
INPUTS: 
Ten universal inputs, configurable for 0-5VDC, 0-20mA, or thermistor. 
 
ENVIRONMENTAL  
OPERATING RANGE:
  0
° to 130° F (-17.8° to 54.4° C), 10 to 90% relative humidity, non-condensing 
 
COMMUNICATION: 
One (1) CMnet EIA-485 Port - Control Module network screw terminals 
 
Switch selectable baud rates ARC156 / 9600 or 38.4bps 
Recommended wire is: MAGNUM Cable pn A3-ARC-156-2 
 
(10)  Analog and/or Digital - screw terminals 
 
 
Jumper Selectable inputs 
 
 
Thermistor - 10k ohm @ 77
° F, 25°C 
 
 
0 to 5 VDC - 10k ohm max source impedance 
 
 
4 to 20mA -  24VDC loop power, 250 ohm input 
 
 
Dry Contact - 0.5mA sense current 
 
MEMORY: 
1 MB Flash Memory, 1 MB Non-volatile battery backed RAM. 
 
PROTECTION:
 
Voltage, current, and ESD protection on incoming power. 
 
BATTERY: 
Seven-year lithium battery provides a minimum of 10,000 hours of data 
 
retention during power outages. 
  Liebert Corporation