Installation
4
2.0
I
NSTALLATION
2.1
Install a Liebert IntelliSlot Web Card—Non-Adapter Version
Follow these steps to install a Liebert IntelliSlot Web card (non-adapter version—P/N IS-WEBCARD, 
IS-WEBLB and IS-WEBLBDS).
1. Locate the Liebert IntelliSlot option bay on your Liebert equipment—You might need to remove a 
plastic cover.
2. Insert the Liebert IntelliSlot Web Card into the Liebert IntelliSlot bay.
3. Secure the card with the supplied screws.
4. Connect an Ethernet cable.
DHCP: The card ships with DHCP service enabled. The MAC address is on a 
sticker on the top of the card.
OR
Static IP: To assign a static IP address or hostname, use terminal emulation 
software to configure the card, as described in Sections 2.1.1 and  2.1.2.
2.1.1 Connect the Cable
1. Locate the blue serial configuration cable (null modem) that shipped with the 
card.
2. Connect the configuration cable to the DB-9 port on the card and to a COM port 
on your PC.
2.1.2 Prepare the Card for Configuration
• Use terminal emulation software, such as 
Microsoft
®
 HyperTerminal, to open a 
connection to the card with the settings in 
• Press the Enter key for the Main Menu, above 
right.
• Select IP Network Settings, then Boot/IP 
Settings and follow the instructions to enter 
an IP ADDRESS, NETMASK and GATEWAY.
• Press Esc to return to the Main Menu.
• Choose Exit and Save to save your changes 
and reboot the card.
!
WARNING
Only a qualified service professional should install these products. Liebert recommends 
having a Liebert Services representative perform the installation in large UPSs. Contact 
Liebert Services at 1-800-LIEBERT (1-800-543-2378).
Table 2
Communication settings
Baud Rate:
9600
Data Bits:
8
Parity:
None
Stop Bits:
1
Flow Control:
None
NOTE
When installing the card in a Liebert NX
configure the communication port of NX to 
2400 baud. See the NX user manual for 
details.