Emerson Xtreme Density Manuel D’Utilisation

Page de 84
Designing a Liebert XD Solution
29
3.18 Chilled Water Piping
The Liebert XDP is offered only with a two-way chilled water control valve. Some applications may 
require the use of a pressure activated bypass valve, to prevent dead-heading of the chilled water 
pump. This bypass valve must be specified by the engineer responsible for design of the chilled water 
field piping system.
Chilled water connections to the Liebert XDP are near the bottom of the unit. Refer to the Liebert 
XDP user manual (SL-16641) for further information. Piping is routed downward from the unit to 
chilled water piping under the raised floor. Connections are made using standard practices for copper 
chilled water piping. Victaulic
®
 connections may be used to simplify installation in existing facilities. 
Refer to Table 31 for additional information.
3.19 Electrical
Make all wiring and electrical connections in accordance with local and national codes. Refer to the 
applicable table in 5.0 - Specifications regarding wire size and circuit protection requirements. 
Refer to electrical schematic when making connections.
3.20 Display Panel and Remote Temperature/Humidity Sensor Locations
The display panel must always be installed in the conditioned space. The display panel may be 
mounted on the Liebert XDC/XDP’s front door if the unit is located in the area that it conditions.
The remote temperature / humidity sensor for the Liebert XDP and the Liebert XDC should be located 
in the higher-temperature portion of the cold aisle where the XD modules are located. Alternatively, it 
can be placed on the return air side of the primary air mover (e.g., Liebert Deluxe System/3
) in the 
room if it represents the conditions where all the XD cooling modules are located. It should not be 
installed where ambient air might cause false readings, for example, near unsealed doors, windows 
and similar areas.
Table 14
Outdoor condenser charge—R-407c
Model
Charge / Circuit, lb (kg)
CDL830
200 (90.8)
CSL616
254 (115.2)
CSL415
200 (90.8)
Table 15
Air cooled systems - liquid line charge - R-407c refrigerant per 100 ft (30 m) of Type "L" 
copper tube
O.D.,
inches
Liquid Line,
lb (kg)
Hot Gas Line,
lb (kg)
3/8
3.7 (1.7)
-
1/2
6.9 (3.1)
-
5/8
11.0 (5.0
2.2 (1.0)
3/4
15.7 (7.1)
3.1 (1.4)
7/8
23.0 (10.4)
17.5 (8.0)
1-1/8
39.3 (17.8)
7.8 (3.5)
1-3/8
59.8 (27.1
11.8 (5.4)
1-5/8
-
16.7 (7.6)
Table 16
Indoor water/glycol cooled module – R-407c refrigerant charge
Model 60 Hz
Charge / Circuit, lb(kg)
Liebert XDC 160
30.0 (13.2) per circuit