Emerson Xtreme Density Manuel D’Utilisation

Page de 84
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
51
4.10 Liebert XDP Standard Features
• Heat Exchanger—Brazed plate design with interwoven circuiting constructed of stainless steel 
plates, copper brazed.
• Pumps—Centrifugal type, end suction, internally cooled, canned rotor design.
• Standard Control Processor—The standard control system is microprocessor-based with an exter-
nal LCD numerical display to allow observation of specified adjustable functions. Operating con-
ditions and status are indicated on the LCD panel, which is mounted either on the unit or on the 
wall, depending on application details (see user manual, SL-16641). The control system also mon-
itors unit operation and activates an alarm when any of the specified factory preset conditions are 
exceeded.
• Cabinet and Frame—Custom powder painted steel panels. A hinged control access panel opens to 
a second front panel, which is a protected enclosure for all high voltage components. Frame is con-
structed of 14 gauge heliarc welded tubular steel and painted using an auto-deposition coating 
system.
Figure 50 Liebert XDP dimensions
Table 22
Liebert XDP dimensions
Model
50/60Hz
Dimensional Data inches (mm)
Shipping Weight, lb (kg)
 A
B
C
 D
 E
Domestic
Export
Liebert 
XDP160
 38 (965)
 34 (864)
33-1/8 (841)
33 (838)
36 (914)
990 (449)
1067 (484)
* The dimension does not include the bezel of the disconnect switch.
Unit Dimensional Data
Floor Cutout Dimensions
E
D
A
Overall
C
Side Panel
B
Overall
DPN000767
Pg. 2, Rev. 6
D
Unit Base
E
Unit Base
78"
(1981mm)
11"
(279mm)
5" (
127
mm
)
1" (25mm)
5-1/2"
(140mm)
The shaded area indicates
a recommended clearance
of 36" (914mm) for component
access.