Emerson Xtreme Density Manuel D’Utilisation

Page de 84
Specifications
66
Table 30
Floor stand specifications—Liebert XDC with 40% ethylene glycol
Models - 60 Hz
XDC160 Glycol Floor Stand - 60Hz - 40% EG
Outside Ambient °F (°C)
95 (35)
100 (38)
105 (41)
Entering Fluid Temp °F (°C)
110 (43)
110 (43)
110 (43)
Performance Data
Cooling capacity, tons (kW)
42.5 (149.4)
Total Heat Rejection, (kW)
192.6
Flow, GPM
204
Pressure Drop, psi (ft water)
35.9 (82.9)
Heat Rejection Equipment
Drycooler
DNT 940A
2 x DNT 880A*
Drycooler Pressure Drop, psi (ft water)
6.5 (15.1)
2.7 (6.3)
Glycol pump package - 10HP
9A31258G3
Pump Control Package - 208V
9A34606G47
Pump Control Package - 460V
9A32114G4
Pump Total Head @ 204 GPM, ft water
145
Water regulating valve size
1-1/4"
Piping Connections
Water / glycol supply and return lines
2-5/8"
* When multiple drycoolers are used ensure flow is balanced.