Specifications
72
Table 37
Liebert XDV10 specifications
Models
XDV10BK--*; XDV10DK--*
XDV10BKP-*; XDV10DKP-*
XDV10BK-E*; XDV10DK-E*
XDV10BKPE*; XDV10DKPE*
XDV10BKR-*; XDV10BKRE*
XDV10DKR-*; XDV10DKRE*
XDV10BT--*; XDV10DT--*
XDV10BTP-*; XDV10DTP-*
XDV10BT-E*; XDV10DT-E*
XDV10BTPE*; XDV10DTPE*
XDV10BTR-*; XDV10BTRE*
XDV10DTR-*; XDV10DTRE*
XDV10BS--*; XDV10DS--*
XDV10BSP-*; XDV10DSP-*
XDV10BS-E*; XDV10DS-E*
XDV10BSPE*; XDV10DSPE*
XDV10BSR-*; XDV10BSRE*
XDV10DSR-*; XDV10DSRE*
60 Hz
60 Hz
50 Hz
50 Hz
Cooling Capacity
Nominal (98ºF [37ºC] EAT): 10kW / 2.8 Tons
Maximum (106ºF [41ºC] EAT): 11.8kW/3.4 Tons
Nominal (98ºF [37ºC] EAT): 8kW / 2.3 Tons
Maximum (116ºF [47ºC] EAT): 11.8kW/3.4 Tons
Conditions
 Capacity Rating is @ 55ºF (13ºC) Entering Fluid Temperature and
50ºF (10ºC) or lower dew point, rear air inlet.
Electrical Requirements
Input
120V model: 1ph-60 Hz
230V model: 
1ph-60 Hz
230V model: 1ph-50 Hz
Input power connections
2 power connections, each model
Full Load Amps
120V model: 2.0A
230V model: 1.0A
Power consumption,
nominal, watts
180
190
190
190
Dimensions, inches (mm)
Height – unit only
14 (355) not including pipe connections
Height – including hard
pipe connections
18-5/8 (473)
Height – including one-
shot connections
19-5/8 (498)
Width
22-7/8 (581)
Depth – Top
39-1/2 (1003)
Depth – Bottom
29-5/8 (752)
Weight, lb (kg)
Unit only
77 (35)
Shipping weight
125 (57)
Installed, with refrigerant
79 (36)
Number of fans
2
2
2
2
Airflow, Nominal,
ft
3
/ min (m
3
/ hr)
1000 (1699) with rear inlet. Bottom inlet airflow 
may be less, depending on restrictions inside 
cabinet
833 (1415) with rear inlet. Bottom inlet airflow 
may be less, depending on restrictions inside 
cabinet
Audible noise
78 dBa sound power
73 dBa sound power
Pipe Connections (without Liebert Flex Pipe)
Refrigerant supply
from Liebert XDP/ XDC
1/2" OD, Cu, (optional 1/2" threaded coupler flex piping)
Refrigerant return
to Liebert XDP/ XDC
5/8" OD, Cu, (optional 3/4" threaded coupler flex piping)
Serviceable Parts
Fans and electrical components
Cabinet Exterior Finish
Black, matte finish, heat-fused powder coat
Options
Condensate sensing
(factory-installed)
Dry contact outgoing signal
Pre-Charged Refrigerant
R-134a Refrigerant, one-shot connections
Agency
Approvals
CSA 60Hz
CSA 50Hz
CE 50Hz
* = Revision level of unit