Table 4. Q7330/M91XX Checkout Procedure.
Step
Proper Motor Response for Normally 
Closed Motor
Proper Motor Response for Normally 
Open Motor
1. Disconnect leads from terminals 
1,2,3,4.
Motor closes. (Fully ccw
 as 
viewed from power end).
Motor opens. (Fully cw
 as viewed 
from the power end)
2. With motor powered jumper terminals 1 
and 2.
Motor drives open (clockwise
 as 
viewed from powered end).
Motor drives closed (counterclockwise 
 as viewed from the power end).
3. Remove either T terminal or disconnect 
power supply.
Spring return motors return to normal spring position (fully ccw
 for 
mechanically normally closed motors, fully cw
 for mechanically normally 
open motors.
4. Jumper terminals 1 and 3.
Motor drives closed.
Motor drives open.