Communications Installation - RS-485 Link to Operator Interface 
Revision 5 
  HC900 Hybrid Controller Installation and User Guide 
101 
9/03  
C. Direct Ethernet Connection to one HC900 controller 
 
Ethernet 10 Base-T
Crossover cable
Defaults:
IP Address: 192.168.1.254
Subnet Mask: 255.255.255.0
Default Gateway: 0.0.0.0
Host 10Base-T Ethernet port, RJ-45 connector
 
Step Procedure 
Make sure the PC has an Ethernet NIC (Network Interface Card) installed and enabled.  
Connect an Ethernet 10Base-T crossover cable to the HC900 controller’s Open Ethernet RJ-45 port 
(top RJ-45 port). 
Connect the other end of the Ethernet 10Base-T crossover cable to the PC’s network port. 
On the PC, use the Utilities Worksheet in the HC Designer software to connect to the controller over 
Ethernet. Every HC900 controller is shipped with the default IP address of 192.168.1.254 and Subnet 
Mask of 255.255.255.0.   You can use these network parameters initially for testing or configuration 
use.  In the Current PC to Controller Connection Settings area of the dialog box, click on the Network 
button to bring up the Network Port Properties dialog box and Add the default IP address. Be sure the 
Ethernet Network Interface Card in the PC has a fixed IP address on the same subnet as the 
controller (192.168.1.x, where x= 2 to 253).   
In the Current PC to Controller Connection Settings area of the dialog box, select  Network for the 
Port to be used and the default IP address for the Address.  Click on Loopback to assure 
communications between the PC and the controller.  You may now use the Ethernet port for 
configuration interface.  
 
 
Consult your IT systems administrator for allocating IP addresses if this controller will require a 
unique IP address within a plant network. Be also sure that the PC Network Interface Card has an IP 
address that allows access to the controller on the subnet after changing the controller’s network 
parameters. 
You may change the controller’s IP address and related network parameters from its default using 
the Utilities Worksheet in the HC Designer software. This may be done using either the RS-232 serial 
port (typically used) via a null modem cable connection or the Ethernet connection from the PC to the 
controller.  If the RS-232 connection is desired, make sure the proper PC serial Com port to be used 
has been set up (See Direct Serial RS-232 Connection above).