Specifications - Environmental and Operating Conditions 
170 
  HC900 Hybrid Controller Installation and User Guide 
Revision 5 
  
9/03 
Environmental and Operating Conditions  
 
Parameter Reference 
Rated 
Extreme 
Transportation 
and Storage 
Ambient Temp. 
 
       °F 
 
       °C 
 
77 ± 5 
25 ± 3 
 
32 to 131 
0 to 55 
 
32 to 140 
0 to 60 
 
–40 to 151 
–40 to 66 
Ambient Relative 
Humidity * 
10 % to 55 % RH 
non-condensing 
10 % to 90 % RH 
non-condensing 
5 % to 90 % RH 
non-condensing 
5 % to 95 % RH
non-condensing 
Mechanical 
   Acceleration 
   Duration 
 
0 g 
0 ms 
 
1 g 
30 ms 
 
5 g 
30 ms 
 
20 g 
30 ms 
Vibration 
10 Hz to 60 Hz—
amplitude 0.07 mm 
(peak-to-peak) 
0 Hz to 14 Hz—amplitude 
2.5 mm (peak-to-peak) 
 
 
 
60 Hz to 150 Hz—
acceleration 1 g 
14 Hz to 250 Hz—
acceleration 1 g 
 
 
Power 
Voltage 
 
Frequency  
Power Consumption 
100 V to 240 V (24 V 
optional) 
50/60 Hz 
110 VA typical 115VAC 
 
 
 
*Relative Humidity is de-rated above 40 °C. 
 
Module “T” Rating for Class 1, Div. 2, groups A, B, C, D 
Analog Input Module – 8 channel 
T6 
Digital Input, Contact type, 16 channel  
T5 
Digital Input, 24Vdc type, 16 channel 
T4 
Digital Input, 120/240 Vac, 16 channel 
T3C @ Ta=60
°C 
T4 @ Ta=40
°C 
Analog Output, 4 channel 
T5 
Digital Output, Relay type, 8 channel 
T5 
Digital Output, 24Vdc, 16 channel 
T4 
Digital Output, 120/240Vac, 8 channel 
T4