Honeywell DCP552 Mark II Manuel D’Utilisation

Page de 247
User name
:
Preparation date
:
Equipment name
:
Product name
:
Model  No.
:
DCP552
Tag name
:
Instrumentation staffer in charge :
Business staffer in charge :
1
DCP552 Parameter Work Sheet
Variable parameter setting
No. Item code
Item
Factory default User
Settings and descriptions
settings
settings
1
PA 01
Key lock
0
0 : Keylock disabled
1 : Display of setup data settings disabled
2 : Display of all settings disabled
3 : Display of all settings disabled. Operation keys disabled.
2
PA 02
Memory protect
0
0 : Disabled
1 : Program settings are protected.
2 : Setup, variable parameters and event configuration 
settings are protected.
3 : Setup, variable parameters, event configurations
and program settings are protected.
4 : Setup, variable parameters, event configurations
and PID parameter settings are protected.
5 : Program settings and all parameter settings are protected.
3
PA 03
Display channel setting
0
0 : 2 items are displayed for the selected CH
1 : Simultaneous 2CH display of the same item
4
PA 04
Synchronous 2 channel 
0
0 : asynchronous
operation
1 : synchronous
5
PA 05
Program auto load
0
0 : OFF
1 : ON
8
PA 08
Auto-tuning (CH1)
0
0 : AT not performed
1 : Standard AT performed on currently used PID group 
in mode other than READY mode
2 : AT writing overshoot-proof PID values to currently used 
PID groups in mode other than READY mode performed
3 : Standard AT performed on PID groups A1 to A7 in 
READY mode
4 : AT writing overshoot-proof PID values to PID groups 
A1 to A7 in READY mode continuously performed
9
PA 09
Auto-tuning MV lower limit (CH1)
0.0
–5.0 to upper limit %
10
PA 10
Auto-tuning MV higher limit (CH1) 100.0
Lower limit to +105%
11
PA 11
SP bias (CH1)
0 SPU
–10000 to +10000 SPU (CH1)
12
PA 12
PV digital filter (CH1)
0.0
0.0 to 120.0sec
13
PA 13
PV bias (CH1)
0 PVU
–1000 to +1000 PVU(PV1)
14
PA 14
Manipulated variable deviation  110.0
0.1 to 110.0% OUT / 0.1sec 
limit (CH1)
15
PA 15
Time proportional output cycle (CH1) 10
1 to 240sec
16
PA 16
On-off control differential (CH1) 50 SPU
0 to 1000 SPUm (CH1)
17
PA 17
PID computation initialize 
0.0
–5.0 to +105.0%
manipulated variable (CH1)
21
PA 21
SP bias (CH2)
0
-10000 to +10000 SPU (CH2)
22
PA 22
PV digital filter (CH2)
0.0
0.0 to 120.0sec
23
PA 23
PV bias (CH2)
0 PVU
–1000 to +1000 PVU(PV2)
24
PA 24
Manipulated variable 
110.0
0.1 to 110.0% OUT/0.1 sec
deviation limit (CH2)
25
PA 25
Time proportional output 
10
1 to 240sec
cycle (CH2)
26
PA 26
ON-OFF control differential 
50
0 to 1000 SPU (CH2)
(CH2)
27
PA 27
PID computation initialize 
0.0
-5.0 to +105.0%
manipulated variable (CH2)
31
PA 31
Group 1 event number
0
0 to 16
(0: No delay is specified.)
32
PA 32
Group 1 delay time
0.0
0.0 to 3000.0sec
33
PA 33
Group 2 event number
0
0 to 16
(0: No delay is specified.)
34
PA 34
Group 2 delay time
0.0
0.0 to 3000.0sec
35
PA 35
Group 3 event number
0
0 to 16
(0: No delay is specified.)