4  -  9
Event Output (Open Collector Output) Connection
Handling Precautions
• Do not short-circuit the positive (+) terminal of the external power supply
to terminals (5) to (8), (17) to (20), (10), (11), (22), (23), (27), (28), (31),
and (32) on the 
DCP552
. Doing so causes the open collector outputs to
malfunction. (There is no short-circuit preventing circuit inside.)
• When connecting a semiconductor load such as a programmable
controller (sequencer), select a module in which the current directions
match.
Use one made inoperative by the leakage current produced when the
digital outputs are shut off.
4-11
5
+
6
7
8
17 18 19 20
9
EV1  EV2  EV3   EV4  EV5   EV6   EV7   EV8
External power supply
12 to 24V DC
Max. load current             
Max. common current        
Leakage current when OFF
External power supply
12 to 24V DC
Max. load current            
Max. common current       
Leakage current when OFF
10
+
11 22 23 27 28 31 32 24
EV9   EV10  EV11  EV12  EV13  EV14  EV15  EV16
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
Load
: 70mA/point
: 500mA
: less than 0.1mA
: 70mA/point
: 500mA
: less than 0.1mA