Honeywell DCP552 Mark II Manuel D’Utilisation

Page de 247
5  -  3
Mode
5-24
■ Mode types
Modes are listed below.
● Program operation
The program is run according to SP, time, events and other settings made in
program patterns 1-49.
● Constant value control
The control is run according to SP and events made with the constant value control
data.
● READY
READY indicates that the program is ready to run.
MV becomes fixed and events whose operation depends on values set in the
segments are turned off. Note, however, that DCP552 state dependent events still
run.
Program numbers between 1 to 49 and set segment numbers can be selected during
program operation.
All setup data, some event configuration data and some constant value control data
parameters can be changed in the READY mode.
Memory cards can also be used in the READY mode
Chapter 5. FUNCTIONS
AUTO
MANUAL
Program operation
Mode
READY
AUTO
MANUAL
AUTO
MANUAL
AUTO
MANUAL
AUTO
MANUAL
AUTO
MANUAL
AUTO
MANUAL
AUTO
MANUAL
READY FAST
RUN
HOLD
FAST
END
READY
RUN
Constant value
 control