Default Front Panel Display Screens
 ION 7500 / ION 7600 User’s Guide
Page 28
Chapter 2 - Using The Front Panel 
17. Phasors (Phasors)
This screen is a phasor diagram display that shows the magnitude and the 
relative angular difference between all phase voltage (V a, V b, V c, V 4) and 
current (I a, I b, I c, I 4, I 5) fundamental components.
18. Name Plt (Name Plate Info)
The Name Plate Info screen contains the following information: Owner, 
TAG
 1 
and 
TAG
 2 from the Factory module, firmware revision of the ION meter, and a 
battery life indicator. 
TAG
 1 and 
TAG
 2 typically identify the meter’s user and 
installed location. The Owner and 
TAG
 registers are configurable with the 
Designer software.
19. Events (Event Log)
The Event Log display alerts you to events written to the meter’s event log. 
D
ATE
, T
IME
, S
OURCE
, and E
VENT
 information are provided. The up and down 
Navigation buttons allow you to move through the list.
20. Setpoint (Setpoint Status)
This numeric display screen displays the status of the setpoint parameters 
defined in the Vista Setpoints diagram.
21. Energy2 (Energy Received)
This numeric display screen shows received (exported) energy values for kWh, 
kVARh, and kVAh.
22. Demand2 (Demand Received)
This numeric display screen shows received power quantities (kW, kVAR, and 
kVA) in the present demand period. By default, these values are from a sliding 
window demand (rolling block) calculation.
23. Pk Dmd2 (Peak Demand Rec)
This is a numeric display screen with timestamps. It shows the maximum 
received demand quantities (kW, kVAR, and kVA) and the time at which they 
were recorded. By default, these values are from a sliding window demand 
(rolling block) calculation.
24. THD (Volts and Amps THD)
This numeric display screen contains the total harmonic distortion on all phase 
voltage and current inputs.
25, 26, 27, 28. V1 Harm, V2 Harm, V3 Harm, V4 Harm (Harmonics)
These four histogram display screens show the harmonic content on the phase 
voltage inputs.
29, 30, 31, 32, 33. I1 Harm, I2 Harm, I3 Harm, I4 Harm, I5 Harm (Harmonics)
These five histogram display screens show the harmonic content on the phase 
current inputs.
34. TOU (Active Rate / Season)
This eight parameter display screen shows kWh delivered values for each all 
four of the possible time of use (TOU) rates (rates A, B, C, and D).