 shows a typical example of a CO equipment rack layout using HMS-318 List 3 shelves. The figure 
shows a rack with a fuse panel, eight HMS-318 List 3 shelves, each separated by a two rack space baffle with the 
remaining shelf space open. As the figure illustrates, baffles should be placed between each shelf to reduce the 
chimney heating effect (see 
 for further information about cooling the HMS-318 
List 3 shelf).
Outdoor cabinet applications require forced air to ensure proper cooling.
Figure 1-11. Central Office Equipment Rack Configuration
Note:
 Refer to the respective ADC card user manuals to determine the maximum number of cards that can 
be installed in a shelf before exceeding the maximum heat dissipation density of the telco-style equipment 
rack configuration.