ADC HRM-238 L1 Manuel D’Utilisation
Installation
LTPH-UM-1237-04
6
July 21, 2004
HRM-238 List 1
1
Remove the fuse(s) in the equipment bay fuse panel for the circuit(s) where the HRM-238 shelf battery
wire(s) will terminate.
wire(s) will terminate.
2
Connect one end of the frame ground wire to Terminal 4 (FGND) on TB1 of the HRM-238 shelf and attach
the other end of the frame ground wire to the CO ground wire termination point.
the other end of the frame ground wire to the CO ground wire termination point.
3
Connect the -48 Vdc CO battery to the HRM-238 shelf (
a
Connect a wire to the HRM-238 shelf TB1 Terminal 1 (-48V_A) for Primary CO battery.
b
Connect a wire to the HRM-238 shelf TB1 Terminal 2 (-48V_B) for Redundant CO battery.
c
Connect the battery common wire to HRM-238 shelf TB1 Terminal 3 (BATTERY RETURN) of the
HRM-238 shelf and attach the other end to CO battery ground source(s).
HRM-238 shelf and attach the other end to CO battery ground source(s).
d
Connect the wire(s) from the HRM-238 TB1 Terminal 1 and Terminal 2 to the CO -48 Vdc power
termination point(s).
termination point(s).
Figure 7.
Connect -48 Vdc and Frame Grounds to TB1
I
NSTALLING
C
OMMUNICATION
W
IRING
All wiring and connections for the HRM-238 shelf are on the back.
shows the shelf backplane
and connectors. Connect the NMA wiring from the HRM-238 shelf to each HiGain or Megabit Modem line unit
that will be managed using the steps beginning on
that will be managed using the steps beginning on
. Then, use the other connectors in
and
appropriate for your application.
Table 2.
Terminal Block (TB1)
Terminal
Description
1
-48V_A
2
-48V_B
3
BATTERY RETURN
4
FGND
Terminal 1
to -48 Vdc
to -48 Vdc
H0547-B
Terminal 4 to
frame ground (FGND)
frame ground (FGND)
Terminal 2
to -48 Vdc
to -48 Vdc
Terminal 3 to battery
common (Battery Return)
common (Battery Return)