ADC HRM-238 L1 Manuel D’Utilisation

Page de 26
LTPH-UM-1237-04
 Installation
HRM-238 List 1
July 21, 2004
 11
I
DENTIFYING
 A
LARMS
Alarm relay contacts for each management unit are on J13 and J14 (
). Install wiring between these pins 
and an alarm monitoring device per local practice. 
 describes the alarm J13 and J14 pinouts.
Figure 11.
Alarm Relay Wire-Wrap Pins
T
URNING
 U
P
 
THE
 S
YSTEM
Perform the following procedures prior to installing the management unit(s) into the shelf.
Insert Fuse 
Insert an appropriately sized fuse(s) into the equipment bay fuse panel for the circuit(s) where the HRM-238 shelf 
battery wire(s) were terminated. Refer to the appropriate management unit user manual for power consumption, 
power dissipation, and current drain.
Table 7.
Alarm J13 and J14 Pinouts
Pin
Description
Pin
Description
1
CRIT_AUD_NC_A
13
MIN_AUD_NC_A
2
CRIT_AUD_COM_A
14
MIN_AUD_COM_A
3
CRIT_AUD_NO_A
15
MIN_AUD_NO_A
4
CRIT_VIS_NC_A
16
MIN_VIS_NC_A
5
CRIT_VIS_COM_A
17
MIN_VIS_COM_A
6
CRIT_VIS_NC_A
18
MIN_VIS_NO_A
7
MAJ_AUD_NC_A
19
SYS_ID_NC_A
8
MAJ_AUD_COM_A
20
SYS_ID_COM_A
9
MAJ_AUD_NO_A
21
SYS_ID_NO_A
10
MAJ_VIS_NC_A
22
EXT_ACO_A
11
MAJ_VIS_COM_A
23
LGND
12
MAJ_VIS_NO_A
Alarm relay pins (J13)
Alarm relay pins (J14)
H0651-A