National Instruments BridgeVIEW Manuel D’Utilisation

Page de 455
Appendix A
HMI Function Reference
A-12
© National Instruments Corporation
max priority is the maximum priority of alarms read. If left 
unwired, alarms corresponding to priority level 15 and below are 
reported.
filter ACK alarms? determines whether acknowledged alarms 
are read.
group/tag names determines the tags for which alarm conditions and 
events are read. 
timeout (secs)(1) specifies how many seconds to wait before reading the 
tag alarms and events. If timeout is 0, the alarms and events are read 
immediately. If it is wired, the VI waits indefinitely until a new alarm or 
event occurs or the Real-Time Database shuts down, whichever occurs 
first.
format allows you to compose the alarm message you want to display for 
the tags.
Date determines whether to display the date.
Date Format determines the format of the date, if it is selected for 
displaying.
Time determines whether to display the time.
Time Format determines the format of the time, if it is selected 
for displaying.
Tag Name determines whether to display the name of the tag 
in alarm.
Group Name determines whether to display the name of the 
group that the tag in alarm belongs to.
Alarm Value determines whether to display the value of the tag 
that caused the alarm.
Alarm State determines whether to display the type of alarm 
(HI_HI, LO, etc.).
Alarm Ack State determines whether to display the status of the 
user who acknowledged the alarm. 
Alarm Priority determines whether to display the priority of the 
alarm state.