Siemens SIMATIC NET PROFIBUS Manuel D’Utilisation

Page de 490
32
7 Technical Data
Version 1.0 8/00
OLM Module
P11
G11
G11-1300
P12
G12
G12-1300
G12-EEC
Transmission distance
– with glass fiber E 10/125
0 - 15 000 m
2)
(0.5 dB/km)
– with glass fiber G 50/125
0 - 3 000 m
2)
0 - 10 000 m
(860 nm: 3.0 dB/km; 1310 nm: 1.0 dB/km)
– with glass fiber G 62,5/125
0 - 3 000 m
2)
0 - 10 000 m
(860 nm: 3.5 dB/km; 1310 nm: 1.0 dB/km)
– with PCF fiber S 200/230
Transmitting power ”Reduced“
Transmitting power ”Default“
0 - 400 m
2)
(660 nm: 10.0 dB/km; 860 nm: 8.0 dB/km)
– with plastic fiber S 980/1000
Transmitting power ”Reduced“
0 - 50 m
Transmitting power ”Default“
0 - 80 m
(0.25 dB/m)
Connector
BFOC/2.5
Electromagnetic compatibility (EMC)
Interference emissions
Limit class B (EN 55022)
Interference immunity against static charges
At shielded socket and housing parts: ±8 kV contact discharge 
(EN 61000-4-2)
Immunity against high-frequency interference
– 10 V/m at 80% amplitude modulation with 1 kHz, 
– 
80 MHz - 1 GHz (EN 61000-4-3)
– 10 V/m at 50% on-period at 900 MHz (ENV 50204)
– 10 V/m at 80% amplitude modulation with 1 kHz, 
– 
10 kHz - 80 MHz
Immunity against line-conducted disturbance
On power supply lines and shielded 
(Burst)
RS 485 bus lines: ±2 kV (EN 61000-4-4) 
Immunity against line-conducted disturbance
– On power supply lines: ±1 kV symmetrical 
(Surge)
– On shielded RS 485 bus lines: ±2 kV asymmetrical
– 
(EN 61000-4-5) 
Climatic ambient conditions
Ambient temperature
0 °C to +60 °C (IEC 68-2-1, IEC 68-2-2)
–20 °C to +60 °C at OLM/G12-EEC
1)
(IEC 68-2-1, IEC 68-2-2)
Storage temperature
–40 °C to +70 °C (IEC 68-2-14)
Relative humidity
<95 %, non-condensing (IEC 68-2-30)
100 %, condensing at OLM/G12-EEC
1)
(IEC 68-2-30)
Mechanical ambient conditions
Vibration (during operation)
10 to 58 Hz, 0.075 mm displacement;
58 to 150 Hz, 10 m/s
2
(1 g) acceleration (IEC 68–2–6)
Vibration (during transport)
5 to 9 Hz, 3.5 mm displacement;
9 to 500 Hz, 10 m/s
2
(1 g) acceleration
Protection class
IP 40
Dimensions (W x H x D)
39.5 x 110 x 73.2 mm
Housing material
Die-cast zinc
Weight
approx. 500 g
1) The OLM/G12 can also be supplied in a special design for more severe environmental conditions. This variant is designated the OLM/G12-EEC.
The DIL switches on the OLM/G12-EEC may also only be operated at ambient temperatures between 0°C and + 60°C.
2) The specified distance allowed between two OLMs must not be exceeded regardeless of the optical power budget.
The module does not contain any silicon.