Emerson XWEB5000 Manuel D’Utilisation

Page de 48
 
1592010860 XWEB5000 stp GB r1.1 2012.06.22.doc                                     XWEB5000 
10/48 
 
Right connection: 
 
Figure 3 
Wrong connection: 
 
Figure 4 
Always keep the serial cable away from power cables. 
Always keep the serial cable away from Electro-magnetic or frequency sources. 
Do not connect shield to ground. 
Do not connect the “Gnd (ground)” terminal. 
Remember to draw a map of the line. This will help you to find errors if something 
is wrong. 
The instrument with RS485 have “+” and “-“ terminals, respect the polarity.  
To keep the line balanced it is necessary a 100 Ohm resistor at the end of the line 
(you  ca  use  the  RS  485+  and  RS  485-  terminals  of  the  last  instrument 
connected).