Hitachi 115VAC Manuel D’Utilisation

Page de 16
Chapter 2 
 
 
 
Page 5 of 16 
 
 
Chapter 2 – Installation and Wiring 
 
Orientation to Product Features 
 
Figure 2-1 below shows the physical layout of the 115VIF-3 interface board. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Figure 2-1, Board Layout 
 
 
Installing the Interface Board 
 
WARNING: Remove power from the inverter and wait at least five minutes before moving to the next 
step. Open and remove the lower terminal cover. Confirm that the DC bus is fully discharged before 
proceeding further. Also confirm that the external 115 VAC control circuits are deactivated and locked 
out before proceeding. Otherwise, there is danger of electric shock, injury or death.
 
General 
 
The 115VIF-3 interface board may be used with either the SJ200 or SJ700 series of inverters. Follow the 
appropriate installation instructions on the next pages for the particular model series in which you are installing 
the board. The boards 115 VAC-side wiring (from the pendant) and the corresponding AC input functions are the 
same, regardless of which inverter series you are using. 
 
Note: In the standard version of the 115VIF-3, no connections are made to the terminals marked IN and GND, 
or to terminal AC6. 
 
z z z
z z z
To Inverter 
Terminals
 
P24 
FW/1* 




CM1
 
IN 
 
GND 
A
C1 
A
C2 
A
C3 
A
C4 
A
C5 
A
C6 
NEU 
Terminals AC1 to AC5 
and NEU connect to 
115VAC control lines 
from pendant. AC6 – no 
connection.
24VD
C
UP
DN
ACCEL
DECEL
SPSET
RS
GND
OUTPUTS
2
OC IN 
MA
TING CONN
 
NC 
No connection. 
Terminals to inverter 
24 Vdc logic outputs 
(for custom versions 
* See Instructions 
starting on Page 7 
24VDC 
UP 
DN 
ACCEL 
AC
 IN
PU
TS 
The optional 115VIF-KIT 
includes this 
eight-conductor, 9” long 
pigtail connector, used to 
connect the board to the 
SJ700 logic inputs 
Screw hole for securing 
board when used in 
SJ700. Screw is supplied 
with 115-VIF-KIT 
DECEL 
SPSET 
RS 
GND 
VIOLET 
BLUE 
GREEN 
YELLOW 
ORANGE 
RED 
BROWN 
BLACK