Chapter 4  Programming Communications Requests
TASK:
  This must always be set to zero for the Ethernet Interface
Caution
Entering a number other than zero for TASK may cause the Ethernet Interface to
fail.
OK Output:
  The OK output is set if the PLC CPU was successful in handing off the
COMMREQ to the Ethernet Interface.
FT Output:
  The FT output is set if the PLC (rather than the Ethernet Interface) detects
that the COMMREQ fails.  In this case, the other status indicators are not updated for
this COMMREQ.  See Section 3 for more information.
The COMMREQ Command Block
When the COMMREQ function is initiated, the Command Block is sent from the PLC
CPU to the Ethernet Interface.  The Command Block contains the details of a Channel
Command to be performed by the Interface.
The address in CPU memory of the Command Block is specified by the IN input of the
COMMREQ Function Block.  This address may be in any word-oriented area of memory
(%R, %AI, or %AQ).  The Command Block is set up using an appropriate programming
instruction (the BLOCK MOVE Function Block is recommended).
The Command Block has the following structure:
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
Word 1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Data Block Length (words)
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
Word 2
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
WAIT/NOWAIT Flag = 0
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
Word 3
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
CRS Word Pointer Memory Type
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
Word 4
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
CRS Word Pointer Offset
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
Word 5
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
Word 6
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Reserved
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
Words 7 up to 31
(decimal)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Data Block (Channel Command Details)
When entering information for the Command Block, refer to these  definitions:
(Word 1) Data Block Length:
  This is the length in words of the Data Block portion of the
Command Block (up to 25 words-decimal).  The Data Block portion starts at Word 7 of
the Command Block.  The length is measured from the beginning of  the Data Block at
Word 7, not from the beginning of the Command Block.  The correct value for each com-
mand, and the associated length of each command, is specified in Section 3.
(Word 2) WAIT/NOWAIT Flag:
  This flag must be set to zero for TCP/IP Ethernet Commu-
nications.