Unitary UPS
 (continued)
Load on Mains 2
Normal:
bit 4C4 = 0
Danger:
bit 4C6 = 1
Downgraded:
bit 4C5 = X (N/A)
Load on battery:
bit 4C7 = X (N/A)
Q1 indifferent:
bit 40E = X (N/A)
Rectifier/charger indifferent:
bit 408 = X (N/A)
QF1 indifferent:
bit 400 = X (N/A)
Inverter disconnected:
bit 484 = 0
Q5N closed:
bit 498 = 1
Q3BP open:
bit 497 = 0
Q4S closed:
bit 496 = 1
SS closed:
bit 499 = 1
K2S closed (if available):
bit 494 = 1
Normal:
bit 4C4 = 0
Danger:
bit 4C6 = 1
Downgraded:
bit 4C5 = X (N/A)
Load on battery:
bit 4C7 = X (N/A)
Q1 indifferent:
bit 40E = X (N/A)
Rectifier/charger indifferent:
bit 408 = X (N/A)
QF1 indifferent:
bit 400 = X (N/A)
Inverter connected indifferent:
bit 484 = X (N/A)
Q5N open:
bit 498 = 0
Q3BP closed:
bit 497 = 1
Q4S indifferent:
bit 496 = X (N/A)
SS indifferent:
bit 499 = X (N/A)
K2S indifferent:
bit 494 = X (N/A)
Load on bypass