GE GFK-0787B Manuel D’Utilisation
7
7-13
GFK-0787B
Chapter 7 Programming Information
%M Control References
The application program can use the following %M references to provide information to
the GMR software. The references are located at %M12257 – %M12288.
the GMR software. The references are located at %M12257 – %M12288.
Reference
Nickname
Description
Meaning
%M12257
CONTINU
Continue with initialization
& enable outputs
& enable outputs
%M12258
IORES
Perform I/O Fault Table clear.
See next page.
%M12259
PLCRES
Perform PLC Fault Table
clear.
clear.
At an individual PLC
%M12260
ATMANIN
Autotest Manual Initiate
Initiates a single autotest (both
input and outout) any time it is
turned on, even if the Autotest
Inhibit bit is on.
input and outout) any time it is
turned on, even if the Autotest
Inhibit bit is on.
%M12261
ATINHIB
Autotest inhibit
Prevents the “automatic” autotest
(both input and output) from oc-
curring at the Autotest Interval
specified in the GMR Configura-
tion for as long as this bit is On.
Note: it does not prevent an Au-
totest Manual Initate.
(both input and output) from oc-
curring at the Autotest Interval
specified in the GMR Configura-
tion for as long as this bit is On.
Note: it does not prevent an Au-
totest Manual Initate.
%M12262
REPORT
Report GMR version / status
See description of %M12262 (Re-
port) on page 7-14.
port) on page 7-14.
%M12263
FORCLOG
Force block(s) to log on
See the description of PLC Logon
Control on page 7-17.
Control on page 7-17.
%M12264
PLCRESG
Clear PLC Fault Tables in all
PLCs.
PLCs.
See next page.
%M12265
SDCAN
Cancel I/O Shutdown
If an I/O Shutdown was initiated
by any PLC, turning this bit On
cancels it and prevents the shut-
down from occurring. If this bit is
set continuously, no I/O Shut-
down will be initiated.
by any PLC, turning this bit On
cancels it and prevents the shut-
down from occurring. If this bit is
set continuously, no I/O Shut-
down will be initiated.
%M12266
to
%M12288
Reserved for future GMR
use.
use.
%M12257 (Continue)
When the application program has computed valid outputs that can be sent to output
blocks, the application program must set control bit %M12257 (CONTINUE) to 1. When
this is done, outputs to the blocks are enabled.
blocks, the application program must set control bit %M12257 (CONTINUE) to 1. When
this is done, outputs to the blocks are enabled.