tModular Redundancy Flexible Triple Modular Redundant (TMR) System 
User’s Manual –March 1995
GFK-0787B
PLC Fault Table Messages for GMR
The following tables lists PLC Fault Table messages for GMR.. If you need additional
help, call GE Fanuc Technical Service  at  1–800–828–5747.
Code
Message
Meaning
100
No CPU Clock
There is no PLC clock present
100
No PLC Clock
There is no PLC clock present
101
Illegal state step
Internal GMR error: invalid step
101
Illegal trans code
Internal GMR error: invalid transition code
101
Bad trans x from wwww
Internal GMR error: attempted transition to invalid step
100+
GBC ID
CFPT, 0 attempts wwww
Number of attempts exhausted while trying to send a COMREQ
10009
GMRx ornge GBC g req
Out of range Bus Controller (g) was requested by GMRx module
10009
GMRx bad GBC g req
Unconfigured Bus Controller (g) was requested by GMRx module
10010
GMRx ornge GBC g rel
Out of range Bus Controller (g) was released by the GMRx module
10010
GMRx bad GBC g rel
Unconfigured Bus Controller (g) was released by the GMRx module
10011
GMRx ornge GBC g flt
Out of Range Bus Controller (g) was faulted by the GMRx module
10011
GMRx bad GBC g flt
Unconfigured Bus Controller (s) was faulted by the GMRx module
1
Unauthorized GMR Access
Initialization module was invoked with incorrect password
10102
Incorrect GMR Version
Initialization module was called with incorrect version number
10103
GMR Software Exception
An invalid call number was detected
10104
Invalid GMR Pointer
Initialization module was invoked with invalid pointer for diagnostics area
10109
Prog Checksum Timeout
PLC didn’t calculate the program checksum within 10 seconds
10110
Invalid Bus Address
Initialization detected bus addresses not equal to 29, 30, or 31
10111
Sync Not Possible
Synchronization cannot be performed
10112
Output discrepancy
Output discrepancy detected
10113
Miscomp, no more retries
Sync detected miscompare
10114
GMR Coldstart
GMR is performing coldstart
10115
GMR Warmstart
GMR is performing a warmstart
10116
Cannot get all GBCs
Cannot acquire all GBCs during initialization
10117
Cannot do VME Write
The VME Write to 7F3h was unsuccessful
10119
Invalid Switch Case
An invalid case condition was detected during a switch
10120
Failed Disable Ops
The Disable Outputs command (COMREQ) failed to complete successfully
10121
Failed Enable Ops
The Enable Outputs command (COMREQ) failed to complete successfully
10122
Failed Set GMR Mode
The Set GMR Mode command (COMREQ) failed to complete successfully
10123
Failed DG Dgrams
The Clear Datagrams Dequeue command (COMREQ) failed to complete successfully
10124
Failed Read Address
The Read Bus Address command (COMREQ) failed to complete successfully
10129
Num dequeues = n
N dequeue entries were dequeued at startup
10130
Program mismatch A/B
PLCs A and B program mismatch, C is not online
10131
Program mismatch B/C
PLCs B and C program mismatch, A is not online
10132
Program mismatch A/C
PLCs A and C program mismatch, B is not online
10133
Program mismatch A/B&C
PLC A program mismatch with B and C
10134
Program mismatch B/A&C
PLC B program mismatch with A and C
10135
Program mismatch C/A&B
PLC C program mismatch with A and B
10136
Program mismatch A/B/C
All three PLCs mismatch
10137
Program changed A
PLC A program changed
10138
Program changed B
PLC B program changed
10139
Program changed C
PLC C program changed
10140
Config mismatch A/B
PLCs A&B config mismatch, C not online
10141
Config mismatch B/C
PLCs B and C config mismatch, A is not online
10142
Config mismatch A/C
PLCs A and C config mismatch, B is not online
10143
Config mismatch A/B&C
PLC A config mismatch with B and C
10144
Config mismatch B/A&C
PLC B config mismatch with A and C
10145
Config mismatch C/A&B
PLC C config mismatch with A and B