GE GFK-0787B Manuel D’Utilisation

Page de 209
6
 
6-8
Genius
tModular Redundancy Flexible Triple Modular Redundant (TMR) System
User’s Manual – March 1995
GFK-0787B
GMR Configuration Summary
GMR configuration is described in detail on the following pages. The basic steps are:
1.
Select File to create a New System configuration
2.
In the System menu, create the CPU configuration
H CPU Type (788 / 789)
H Number of CPUs (1 – 3)
H Watchdog timer (must match PLC configuration)
H Enable or disable online programming.
H Simplex shutdown (enable/disable)
H Timeout (0 – 65535 seconds)
Select [O]K or [C]ancel to quit the CPU Configuration window
3.
In the System menu, select Autotest Interval and Register
4.
In the System menu, select Input Discrepancy Filter Time
5.
In the System menu, specify the I/O Configuration Limits
H Number of Voted Discrete Input Groups for that GBC group
H Number of Voted Discrete Output Groups for that GBC group
H Number of Analog Input Groups for that GBC group
H Number of words of %AI memory (must match PLC configuration)
H Number of registers of %R memory (must match PLC configuration)
Select [O]K or [C]ancel to quit the I/O Config window
6.
In the System menu, specify the Initialization Data
H Rack and slot locations of the two bus controllers that will be exchanging global data
H %R and %M references and lengths for startup initialization data
Select [O]K or [C]ancel to quit the Initialize Data window
7.
In the System menu, specify the initialization Fault Actions
H Data fault (diagnostic or fatal)
H System fault (diagnostic or fatal)
Select [O]K or [C]ancel to quit the Fault Actions window.
8.
In the System menu, specify Write Access.