APC AR8136BLK200 Manuel D’Utilisation

Page de 44
18.
Select UPS out of Bypass and press ENTER.
Turn UPS Off
Reboot UPS
→ UPS out of Bypass
UPS to Sleep
19.
Confirm by selecting Yes, Out of Bypass and
press ENTER.
Confirm:
UPS out of Bypass?
>NO, ABORT
→ >YES, Out of Bypass
20.
Wait for the UPS to transfer out of bypass.
Putting UPS out of
Bypass, please
wait....
21.
The UPS is now out of bypass and is in normal
operation.
UPS is now out of
bypass
Press any key....
18
Symmetra™ PX48, 96, and 160 kW 400 V 100 kW 208 V Operation
990–3015E-001