Siemens 7ML19985AB01 Manuel D’Utilisation

Page de 112
SIMPLE EXPONENTIAL DEVICES,  P3 = 0
TYPICAL LEOPOLD LAGCO
For rated flows under free flow conditions, the head is measured at a point upstream
referenced to the beginning of the converging section. Refer to the following table.
converging
side
front
0
head
transducer *
diverging
plan
Q
throat
point of measurement
Flume Size
Point of Measurement
(pipe dia. in inches)
mm
inches
4 - 12
25
1.0
15
32
1.3
18
38
1.5
21
44
1.8
24
51
2.1
30
64
2.5
36
76
3.0
42
89
3.5
48
102
4.0
54
114
4.5
60
127
5.0
66
140
5.5
72
152
6.0
* The transducer must be above the maximum head by at least the 
   blanking value, P47.
7ML19985AB01
OCM III
57