Troubleshooting/FAQs 
 
14.2 Problems when Using Modules of Third-party Manufacturers 
 
SIMATIC Panel PC 877 
14-2
 
Operating instructions, Release 07/2006, A5E00877780-01 
14.2 
14.2 
Problems when Using Modules of Third-party Manufacturers 
 
 
Problem 
Possible causes 
To correct or avoid error 
Check your computer configuration: 
• 
If the computer configuration corresponds with factory state, 
please contact your technical support team. 
• 
If the computer configuration has changed, restore the 
original factory settings. Remove all third-party modules, 
then restart the PC. If the error no longer occurs, the third-
party module was the cause of the fault. Replace this 
module with a Siemens module or contact the module 
supplier. 
• 
Force a “Reset Configuration” using the BIOS setup. 
• 
I/O addresses are assigned 
twice. 
• 
Hardware interrupts and/or DMA 
channels are assigned twice. 
• 
Signal frequencies or signal 
levels are incorrect. 
• 
Connector assignments deviate. 
• 
“Reset Configuration” in BIOS 
SETUP has not been carried 
out. 
If the PC still crashes, contact your technical support team. 
 
The PC crashes 
during startup 
• 
If the performance of the 
external 24 V power supply is 
insufficient 
• 
use a larger power supply.