Connecting and Switching On the Panel PC 670/870 
Release 11/02 
2–6 
SIMATIC Panel PC 670/870 Start-Up Instructions 
  
 
Operation 
The operating unit is operated by touching the touch-sensitive screen which 
contains application-specific functions, e.g. touching a button displayed.  
Continue with Step 11. 
 
2.4 Power 
Supply 
Connection Step 
11 
The Panel PC 670/870 can be operated on AC-120/230 V power supplies. The 
voltage selection is performed automatically. 
Plug the power cable in the AC/DC power supply connection on the computer 
unit – in the case of a decentralized design, also in the operating unit's AC/DC 
power supply connection. 
Danger 
Since the operating unit does not have a power switch, turning off and 
completely disconnecting power requires pulling the power plug. 
This location should be easily accessible. For the installation in a cabinet, a 
central power disconnect switch must be provided. 
Notice 
As soon as power is supplied to the operating unit via the power supply 
connection, the BIOS and operating system installed are loaded. 
If the power supply is switched off during this routine, the operating unit is not 
shut down properly. The Scandisk program must then be activated. 
To prevent an unintentional unplugging of the power plug from the computer 
unit, we recommend using the power plug lock contained in the accessories kit. 
In the case of the decentralized design, the operating unit is provided with 
cable clips to fasten the power plug. 
Notice 
A ferrite core is contained in the material supplied with the Panel PC 670. 
Connect the ferrite core supplied directly behind the device socket of the power 
supply cable.  
The operating unit can also be supplied with a DC 24 V power supply, 
according to the order option. Plug the 3-point power supply connector into the 
socket on the Panel PC 670/870. Note the pin assignment depicted on the 
housing. 