Mitsubishi Electronics CR751-D Manuel D’Utilisation

Page de 190
3-91 
  Mode changeover switch input   
3 Controller
3.7 Mode changeover switch input
Connect the key switch of customer prepared and change the right of robot’s operation by switch operation.
The key switch can be installed in the operation panel of customer preparation.
<Right of operation (mode)>
AUTOMATIC.......................The operation from external equipment becomes available. Operation which needs 
the right of operation from T/B cannot be performed. It is necessary to set the 
parameter for the rights of operation to connection with external equipment. Refer 
to the separate volume, "Instruction Manual/Detailed Explanation of Functions and 
Operations" for detail.
MANUAL ..............................When T/B is available, only the operation from T/B becomes available. Operation 
which needs the right of operation from external equipment cannot be performed.
Fig.3-20 : Mode changeover switch image figure (CR751)
(1) Specification of the key switch interface
The function and specification of the key switch interface are shown below.
Table 3-7 : Specification of the mode changeover switch input
Item
Specification
Remarks
Rated voltage
DC24V
Supply from the controller.
Current rating
Approx. 10mA
Select the switch or button which operates normally in 24V/10mA.
Input resistance
Approx. 2.2kΩ
Response time (OFF->ON)
Approx. 15ms
Example: The response time the program starts, after pushing the run button.
Common method
1 point per 
common
Connection method
Connector
Conformity electric wire size
AWG#24 to #18
0.2 to 0.75mm
2
Maker/Type
-
Maker: PHOENIX CONTACT/ Type: FKC2.5/4-STF-5.0B
MODE
MANUAL
AUTOMATIC
Mode changeover switch
(Customer-prepared)
CNUSR1
Table 3-6 : Function of the key switch interface
Pin number and Function (Connector: CNUSR1)
Change mode 
Note1) 
Note1) The mode changes by both opening or both closing between 30-5 pin and between 35-10 
pin. Maintain the current mode except it.
Pin number
Function
MANUAL
AUTOMATIC
49
1st line KEY input
Open
Close
24
Power supply +24V of pin 
number 49
50
2nd line KEY input
Open
Close
25
Power supply +24V of pin 
number 50
[Note] In the customer's system, do not ground the + side of 24V power supply prepared by customer for connect to the 
controller. (related with emergency stop and parallel input/output) If it connects with the controller under the condi
-
tion that the + side is grounded, it will lead to failure of controller.