Emerson BACNET IP Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
114
Table 39
Liebert STS2
, Liebert STS2/PDU
 - Input and Holding - STS2
Controller
STS2
Liebert Products
Liebert STS2
Liebert STS2/PDU
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale 
Notes / Units
Status Points (View)
Total Transfer Count
40001
1
Preferred Source
40002
1
1=Source 1, 2=Source 2
Active Source
40003
1
1=Source 1, 2=Source 2
Source 1 Volts A-B
40004
1
V
Source 1 Volts B-C
40005
1
V
Source 1 Volts C-A
40006
1
V
Source 1 Current A
40007
1
A
Source 1 Current B
40008
1
A
Source 1 Current C
40009
1
A
Source 1 Frequency
40010
1
10
Hz
Source 2 Volts A-B
40011
1
V
Source 2 Volts B-C
40012
1
V
Source 2 Volts C-A
40013
1
V
Source 2 Current A
40014
1
A
Source 2 Current B
40015
1
A
Source 2 Current C
40016
1
A
Source 2 Frequency
40017
1
10
Hz 
Output kW
40018
1
kW
Output kVA
40019
1
kVA
CB 1 Status
40024
1
Bit 0
CB 2 Status
40024
1
Bit 1
CB 3 Status
40024
1
Bit 2
CB 3A Status
40024
1
Bit 3
CB 4 Status
40024
1
Bit 4
CB 5 Status
40024
1
Bit 5
CB Spare 1 Status
40024
1
Bit 6
CB Spare 2 Status
40024
1
Bit 7
CB 7 Status
40024
1
Bit 8
CB 8 Status
40024
1
Bit 9
Auto Xfer Enabled 
40025
1
Bit 0
Has Dual Out Breakers
40025
1
Bit 1
Has PDU Equipped
40025
1
Bit 2
Has 4 pole Switch
40025
1
Bit 3
Has Shunt Trip
40025
1
Bit 4
Has Wye Out Xfmr
40025
1
Bit 5
Has Rmt Sorce Sel
40025
1
Bit 6
Manual I peak Reset
40025
1
Bit 7
Auto Restart Enabled
40025
1
Bit 8