Emerson BACNET IP Manuel D’Utilisation
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
196
Bypass Current L2
30210
—
1
—
A
Output Voltage L2
30213
—
1
—
V
Output Current L2
30214
—
1
—
A
Input Voltage L3
30253
—
1
—
V
Input Current L3
30254
—
1
—
A
Bypass Voltage L3
30259
—
1
—
V
Bypass Current L3
30260
—
1
—
A
Output Voltage L3
30263
—
1
—
V
Output Current L3
30264
—
1
—
A
Black Out Count
30301
—
1
—
—
Brown Out Count
30302
—
1
—
—
Transient Count
30301
—
1
—
—
Silent Audible Alarm
—
40101
—
—
Any value
Battery Start
—
40102
1
—
1=Start, 0=Abort
Open UPS Output Switch
—
40104
—
—
Delay time in Seconds, last digit will be
ignored
Reboot UPS Output Switch
—
40105
1
—
Delay time in Seconds, last digit will be
ignored
Close UPS Output Switch
—
40106
—
—
Delay time in Seconds, last digit will be
ignored
Transfer Load to Bypass
—
40107
1
—
Any value
Transfer Load to Inverter
—
40108
—
—
Any value
Reset UPS Statistic data
—
40111
1
—
Any value
Turn UPS Outlets On
—
40112
1
—
Bitmap mask for Outlet 1-16. All bits set to 1
will be turned On
Turn UPS Outlets Off
—
40113
1
—
Bitmap mask for Outlet 1-16. All bits set to 1
will be turned Off
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 66
Liebert Series 300
™
UPS - Input and Holding (continued)
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units