BACnet Communications - Thermal Management Products
257
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Remote Sensors 10
Remote Sensor Issue
Binary_Value
151
5060_10
RD
Active on Alarm
Compressor
Compressor 1 High Head Pressure
Binary_Value
162
4669_1
RD
Active on Alarm
Compressor 1 Low Suction Pressure
Binary_Value
163
5062_1
RD
Active on Alarm
Compressor 1 Hours Exceeded
Binary_Value
164
5063_1
RD
Active on Alarm
Dig Scroll Comp 1 Temp Sensor Issue
Binary_Value
165
5064_1
RD
Active on Alarm
Dig Scroll Comp 1 Over Temp
Binary_Value
166
5065_1
RD
Active on Alarm
Compressor 1 Low Pressure Transducer Issue
Binary_Value
167
5066_1
RD
Active on Alarm
Compressor 1 High Pressure Transducer Issue
Binary_Value
168
5148_1
RD
Active on Alarm
Ext Compressor Lockout
Binary_Value
169
5067_1
RD
Active on Alarm
Compressor 1 Short Cycle
Binary_Value
170
4681_1
RD
Active on Alarm
Compressor 1 Pump Down Issue
Binary_Value
171
5146_1
RD
Active on Alarm
Reheater
Reheater Over Temperature
Binary_Value
182
5068_1
RD
Active on Alarm
Electric Reheater Hours Exceeded
Binary_Value
183
5069_1
RD
Active on Alarm
Ext Reheat Lockout
Binary_Value
184
5070_1
RD
Active on Alarm
Condenser
Condenser 1 Issue
Binary_Value
195
5071_1
RD
Active on Alarm
Condenser VFD Issue
Binary_Value
196
5072_1
RD
Active on Alarm
Condenser TVSS Issue
Binary_Value
197
5073_1
RD
Active on Alarm
Chilled Water
Supply Chilled Water Over Temp
Binary_Value
208
4626_1
RD
Active on Alarm
Chilled Water Control Valve Position
Binary_Value
209
4703_1
RD
Active on Alarm
Supply Chilled Water Loss of Flow
Binary_Value
210
4980_1
RD
Active on Alarm
System Events
Customer Input 1
Binary_Value
221
4270_1
RD
Active on Alarm
Customer Input 2
Binary_Value
222
4271_1
RD
Active on Alarm
Customer Input 3
Binary_Value
223
4272_1
RD
Active on Alarm
Customer Input 4
Binary_Value
224
4273_1
RD
Active on Alarm
Smoke Detected
Binary_Value
225
4720_1
RD
Active on Alarm
Water Under Floor
Binary_Value
226
4723_1
RD
Active on Alarm
Service Required
Binary_Value
227
4726_1
RD
Active on Alarm
Shutdown - Loss Of Power
Binary_Value
228
4714_1
RD
Active on Alarm
Ext Over Temperature
Binary_Value
229
5104_1
RD
Active on Alarm
Ext Loss of Flow
Binary_Value
230
5105_1
RD
Active on Alarm
Ext Condenser Pump High Water
Binary_Value
231
5106_1
RD
Active on Alarm
Ext Standby Glycol Pump On
Binary_Value
232
5107_1
RD
Active on Alarm
External Fire Detected
Binary_Value
233
5108_1
RD
Active on Alarm
Unit On
Binary_Value
234
5109_1
RD
Active on Alarm
Unit Off
Binary_Value
235
5110_1
RD
Active on Alarm
Unit Standby
Binary_Value
236
5111_1
RD
Active on Alarm
Table 83
Liebert CRV
 - Binary Data (continued)
Controller Liebert iCOM
®
 v4
Data Label
Object Type
Instance
Object
Name
Access
Notes