Emerson BACNET IP Manuel D’Utilisation
BACnet Communications - UPS Systems
339
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
SCC Event Summary
Summary of any active user alarms or faults on the SCC
Schedule Action - ECO Mode
This setting gives the user the ability to choose the action of a schedule
entry to be either stop or start.
Schedule Day of Week - ECO Mode
This setting represents the day of the week when an associated ECO Mode
schedule entry action will take effect.
Schedule Hour - ECO Mode
This setting represents the hour of the day when an associated schedule
entry action will take effect.
Schedule Minute - ECO Mode
This setting represents the minute of the hour when an associated schedule
entry action will take effect.
Schedule Operation State - ECO Mode
This setting gives the user the ability to either enable or disable a schedule
entry if the action is Start.
Service Code Active
Service code is running
Service Required
Unit requires servicing.
Static Bypass Switch
Static Bypass Switch state - On/Off
Static Switch Type
Static switch type configuration
Sum of MMS Output RMS Currents for Phase A The sum of the multi-module system output RMS currents for phase A
Sum of MMS Output RMS Currents for Phase B The sum of the multi-module system output RMS currents for phase B
Sum of MMS Output RMS Currents for Phase C The sum of the multi-module system output RMS currents for phase C
Sum of MMS Output RMS Currents for Phase B The sum of the multi-module system output RMS currents for phase B
Sum of MMS Output RMS Currents for Phase C The sum of the multi-module system output RMS currents for phase C
System Accumulated Energy
Total accumulated energy output for the mms system, since last energy
reset.
System Breaker(s) Close Failure
One or more breakers in the system failed to close
System Breaker(s) Open Failure
One or more breakers in the system failed to open
System Comm Fail
Failure of a device on the multi-module system communication bus
System Controller Error
System controller internal error
System Date and Time
The system date and time
System Fan Failure - Redundant
Redundant system fan failure
System Input Current Imbalance
System Input Currents are Imbalanced
System Input Current Limit
The RMS input current has reached the input current limit threshold
System Input Frequency
The system input frequency
System Input Nominal Frequency
The nominal (or rated) system input frequency
System Input Nominal Voltage The
nominal
(or rated) system input voltage
System Input Phs Rotation Error
The power conductors on the input line are not wired to the UPS in the
sequence preferred for the rectifier (A-B-C)
System Input Power Problem
The input is not qualified to provide power to the system
System Input Power Source
System input power source
System Input RMS A-B
The System Input RMS Voltage between Phase A and Phase B
System Input RMS B-C
The System Input RMS Voltage between Phase B and Phase C
System Input RMS C-A
The System Input RMS Voltage between Phase C and Phase A
System Input RMS Current Phase A
The system input RMS current for Phase A
System Input RMS Current Phase B
The system input RMS current for Phase B
System Input RMS Current Phase C
The system input RMS current for Phase C
System Isolation Output Breaker (IOB)
System isolation output breaker (IOB)
System Load Bank Breaker (LBB)
System load bank breaker (LBB)
System Output Apparent Power
The sum total apparent power of all system output phases
System Output Breaker (UOB)
System output breaker (UOB)
System Output Fault
A fault has been detected in the system output
Table 109 Liebert NXL
™
- 60Hz, UL version (Model 40) - Glossary (continued)
Data Label
Data Description