Emerson BACNET IP Manuel D’Utilisation

Page de 372
BACnet Communications - UPS Systems
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
346
DC Bus
DC Bus Voltage
Analog_Value
66
4148_1
RD
Units: VDC
DC Bus Current
Analog_Value
67
4149_1
RD
Units: A DC
Output
System Output Voltage RMS A-B
Analog_Value
78
4201_1
RD
Units: VAC
System Output Voltage RMS B-C
Analog_Value
79
4202_1
RD
Units: VAC
System Output Voltage RMS C-A
Analog_Value
80
4203_1
RD
Units: VAC
System Output Voltage RMS A-N
Analog_Value
81
4385_1
RD
Units: VAC
System Output Voltage RMS B-N
Analog_Value
82
4386_1
RD
Units: VAC
System Output Voltage RMS C-N
Analog_Value
83
4387_1
RD
Units: VAC
System Output RMS Current Phs A
Analog_Value
84
4204_1
RD
Units: A AC
System Output RMS Current Phs B
Analog_Value
85
4205_1
RD
Units: A AC
System Output RMS Current Phs C
Analog_Value
86
4206_1
RD
Units: A AC
System Output Frequency
Analog_Value
87
4207_1
RD
Units: Hz
System Output Power
Analog_Value
88
4208_1
RD
Units: kW
System Output Apparent Power
Analog_Value
89
4209_1
RD
Units: kVA
System Output Power Factor Phs A
Analog_Value
90
4210_1
RD
 —
System Output Power Factor Phs B
Analog_Value
91
4211_1
RD
 —
System Output Power Factor Phs C
Analog_Value
92
4212_1
RD
 —
System Output Pct Power Phase A
Analog_Value
93
4223_1
RD
Units: %
System Output Pct Power Phase B
Analog_Value
94
4224_1
RD
Units: %
System Output Pct Power Phase C
Analog_Value
95
4225_1
RD
Units: %
System Output Pct Pwr (VA) Phs A
Analog_Value
96
4226_1
RD
Units: %
System Output Pct Pwr (VA) Phs B
Analog_Value
97
4227_1
RD
Units: %
System Output Pct Pwr (VA) Phs C
Analog_Value
98
4228_1
RD
Units: %
Inverter
Inverter Overload Time Remaining
Analog_Value
109
4232_1
RD
Units: sec
Environment
Inlet Air Temperature
Analog_Value
120
4291_1
RD
Units: deg C
Inlet Air Temperature
Analog_Value
10120
4291_1_deg_F
RD
Units: deg F
Total System Operating Time
Analog_Value
121
4292_1
RD
Units: hr
System Date and Time
Analog_Value
122
4293_1
RW
 —
Ratings
Bypass Nominal Voltage
Analog_Value
133
4259_1
RD
Units: VAC
System Input Nominal Voltage
Analog_Value
134
4102_1
RD
Units: VAC
System Input Nominal Frequency
Analog_Value
135
4103_1
RD
Units: Hz
System Output Nominal Voltage
Analog_Value
136
4260_1
RD
Units: VAC
System Output Nominal Frequency
Analog_Value
137
4261_1
RD
Units: Hz
Battery Cell Count - Lead Acid
Analog_Value
138
4262_1
RD
 —
Battery Cell Count-Nickel Cadmium
Analog_Value
139
4263_1
RD
 —
Output Apparent Power Rating
Analog_Value
140
4264_1
RD
Units: kVA
Output Real Power Rating
Analog_Value
141
4265_1
RD
Units: kW
System UPS Module Count
Analog_Value
142
4268_1
RD
 —
System Output Maximum Amp Rating
Analog_Value
143
4267_1
RD
Units: A AC
System Redundant UPS Modules
Analog_Value
144
4269_1
RD
 —
Table 111 Liebert NXL
 - 50 Hz, CE version (Models 48 and 49)—Analog Data
Data Label
Object Type
Instance
Object Name
Access
Notes