Modbus 485 and Modbus IP Protocols - Thermal Management Products
47
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Fan Speed Proportional Band 
Temperature control band above the temperature set point calculated for 
proportional fan speed control. If measured air temperature is within this 
band, fan speed operations are proportionally controlled. 
Fan Speed 
Fan speed expressed as a percentage of the maximum rated speed. 
Heating Proportional Band 
Temperature control band below [Air Temperature Set Point]. If measured 
air temperature is within this band, heating operations are proportionally 
controlled. 
High Power Shutdown 
Supply to high power components has been shutdown. 
High Return Humidity Threshold 
Threshold value used in the [High Return Humidity] event. 
High Return Humidity 
Return air high humidity event. 
Humidification Proportional Band 
Humidity control band below [Humidity Set Point]. If measured humidity is 
within this band, humidification operations are proportionally controlled. 
Humidifier Control Board Not Detected 
Humidifier control board is required to be connected, but no signal is 
detected. 
Humidifier Cylinder Worn 
Humidifier cylinder is not operating properly and needs to be replaced. 
Humidifier Hours Exceeded 
Operating hours for the humidifier have exceeded the threshold. 
Humidifier Issue 
Humidifier issue detected, causing it to be locked out. 
Humidifier Low Water 
The water level in the humidifier has dropped below its threshold. 
Humidifier Over Current 
The electrical current to the humidifier has exceeded its upper threshold. 
Humidifier Under Current 
The electrical current to the humidifier has dropped below its lower 
threshold. 
Humidifier Utilization 
Present humidifier utilization expressed as a percentage of the maximum 
rated capacity. 
Humidity Dead Band 
Value that is divided evenly to form a range above and below [Humidity Set 
Point]. If measured humidity is within this range, no humidification or 
dehumidification will occur. 
Humidity Set Point 
Desired relative humidity. 
Loss of Air Flow 
No air flow through the unit due to failure of all fans. 
Low Return Humidity Threshold 
Threshold value used in the [Low Return Humidity] event. 
Low Return Humidity 
Return air low humidity event. 
Maintenance Completed 
Maintenance has been completed on the unit. 
Maintenance Due 
The calculated maintenance date has been reached. 
Maintenance Ramp 
The ratio of operations performed to the calculated operations available 
between maintenance intervals. 
Master Unit Communication Lost 
Communication with master unit has been lost. 
Operating Efficiency 
The ratio of cooling energy provided to the amount of total energy being 
used. 
RAM Battery Issue 
RAM or RAM backup battery is not operating correctly. 
Reheat Utilization 
Present reheating utilization expressed as a percentage of the maximum 
rated capacity. 
Reheater Over Temperature 
The temperature of the reheater has exceeded its threshold. 
Remote Sensor Average Temperature 
Average value of remote sensor temperature measurements. 
Remote Sensor Function 
Function assigned to remote sensor. Available values are: (0) Control - 
sensor will be used in calculation of remote sensor temperature that may 
be used for heating and cooling control, (1) Reference - sensor will not be 
used in calculation of remote sensor temperature, but is enabled, (2) 
Disable - sensor is disabled 
Remote Sensor Issue 
Remote sensor is disconnected or the signal is out of range. 
Remote Sensor Maximum Temperature 
Maximum value of remote sensor temperature measurements. 
Remote Sensor Minimum Temperature 
Minimum value of remote sensor temperature measurements. 
Remote Sensor Temperature Calculation 
Calculation method applied to temperature readings from the remote 
sensors to determine a single temperature measurement value for cooling 
and heating control. 
Remote Sensor Temperature 
Air temperature as measured by remote sensor. 
Table 13
Liebert CRV
 - Glossary (continued)
Controller
Liebert iCOM
®
 v4
Data Label
Data Description