Emerson BACNET IP Manuel D’Utilisation
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
50
Fluid
Low Fluid Pressure
Low Fluid Pressure
10070
—
1
Active on Alarm
1, 2
Supply (Outlet) Fluid
—
Supply Fluid Over Temp
10081
—
1
Active on Alarm
1, 2
Supply Fluid Under Temp
10082
—
1
Active on Alarm
1, 2
Supply Fluid Temp Sensor Issue
10083
—
1
Active on Alarm
1, 2
Pumps
All Pumps Loss of Flow
All Pumps Loss of Flow
10107
—
1
Active on Alarm
1, 2
Pump 1 Loss of Flow
10108
—
1
Active on Alarm
1, 2
Pump 2 Loss of Flow
10109
—
1
Active on Alarm
1, 2
Pump 1
Pump Hours Exceeded
Pump Hours Exceeded
10120
—
1
Active on Alarm
1, 2
Pump 2
Pump Hours Exceeded
Pump Hours Exceeded
10131
—
1
Active on Alarm
1, 2
Free Cooling
Free Cooling Valve Hours Exceeded
Free Cooling Valve Hours Exceeded
10142
—
1
Active on Alarm
1, 2
Ambient Air Temperature Sensor Issue
10143
—
1
Active on Alarm
1, 2
Evaporators
Evaporator Inlet Temp Sensor Issue
Evaporator Inlet Temp Sensor Issue
10154
—
1
Active on Alarm
1, 2
Evaporator Return Fluid Over Temp
10155
—
1
Active on Alarm
1, 2
Evaporator Return Fluid Under Temp
10156
—
1
Active on Alarm
1, 2
Evaporator 1
—
Evaporator Fluid Freeze - Auto Reset
10165
—
1
Active on Alarm
1, 2
Evaporator Fluid Freeze - Manual Reset Required
10166
—
1
Active on Alarm
1, 2
Supply Refrigerant Temp Sensor Issue
10167
—
1
Active on Alarm
1, 2
Evaporator 2
Evaporator Fluid Freeze - Auto Reset
Evaporator Fluid Freeze - Auto Reset
10178
—
1
Active on Alarm
1, 2
Evaporator Fluid Freeze - Manual Reset Required
10179
—
1
Active on Alarm
1, 2
Supply Refrigerant Temp Sensor Issue
10180
—
1
Active on Alarm
1, 2
System Events
Customer Input 1
Customer Input 1
10191
—
1
Active on Alarm
1, 2
Customer Input 2
10192
—
1
Active on Alarm
1, 2
Customer Input 3
10251
—
1
Active on Alarm
2
Customer Input 4
10252
—
1
Active on Alarm
2
Unit On
10193
—
1
Active on Alarm
1, 2
Unit Off
10194
—
1
Active on Alarm
1, 2
Master Unit Communication Lost
10195
—
1
Active on Alarm
1, 2
Subgroup Event Occurred During Communication Loss
10196
—
1
Active on Alarm
1, 2
Humidifier Control Board Not Detected
10197
—
1
Active on Alarm
1, 2
RAM Battery Issue
10198
—
1
Active on Alarm
1, 2
Unit Code Missing
10199
—
1
Active on Alarm
1, 2
Unspecified General Event
10200
—
1
Active on Alarm
2
Unit Shutdown Unspecified General Event
10250
—
1
Active on Alarm
2
EEV
EEV Unspecified General Event
EEV Unspecified General Event
10270
—
1
Active on Alarm
2
Table 14
Liebert HPC
™
(Chiller) - Status and Coil (continued)
Controller
Liebert iCOM
®
v4
Data Label
Status
Coil
Number
of Bits
Notes
Extra
Notes