Emerson 582145500 Manuel D’Utilisation

Page de 76
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Spec. No: 582145500
14
Section 6040
Model: NetSure™ ITM
Issue AB, April 8, 2013
3.2.3
Mechanical Considerations
The DC UPS system can be comprised of up to four (4) modules (cabinets), depending upon your 
power requirements. All modules used are the same size and are designed to be positioned side-by-
side to form an aesthetically appealing equipment suite. The system always contains one (1) Primary 
Module. For increased power demands, up to three (3) Expansion Modules may be added. Locate the 
Primary Module at the far left or far right of the row. Remove the side panel from the Primary Module 
from the side that will face adjacent Expansion Modules. Place the first Expansion Module next to the 
Primary Module. Place additional Expansion Modules (if required) next to each other. Install the side 
panel removed from the Primary Module to the open side of the last Expansion Module in the row.
Clearances
There are no ventilation grilles on the sides of the DC UPS module. The DC UPS modules may be 
placed with the sides touching or against a wall.
To enable routine tightening of power terminations within the DC UPS module, make sure there is 
sufficient clearance in front and rear of the DC UPS module to permit free passage of personnel and 
that the front door can be fully opened.
Leave a minimum of 8 in. (203mm) between the top of the DC UPS module and the ceiling to permit 
adequate air circulation above the unit. Emerson recommends against using air conditioning or other 
systems that blow air onto the top of the unit.
Leave a minimum of 36 in. (914 mm) between the back of the DC UPS module and a wall to permit 
adequate air circulation for the battery compartment fans and facilitate maintenance access.
3.3
Floor Installation
The diagrams in 2.0 - Installation Drawings and Recommended Tools and Test Equipment 
show the location of holes in the base plate for bolting the DC UPS module to the floor.
If the module is to be placed on a raised floor, it should be mounted on a floor stand that will support 
the equipment point loading. Refer to the cabinet-bottom views in 2.0 - Installation Drawings and 
Recommended Tools and Test Equipment 
to design this pedestal. Contact your Emerson Sales 
Representative for a floor stand designed for this system (see Figure 5).
Figure 5
Emerson Floor Stands
NOTE
When the DC UPS system consists of multiple modules, the switches inside the modules are 
pre-set at the factory to identify the module as the Primary Module, 1st Expansion Module, 2nd 
Expansion Module, or 3rd Expansion Module. When placing modules, refer to the nameplate 
identification number (see Table 1) to ensure the Primary Module is placed on the end, and 
Expansion Modules are place in sequential order.
P/N 547823
36” Tall Floor Stand
P/N 547822
24” Tall Floor Stand