6.3.1
Initially Starting the DC UPS System and Verifying System Operation
The NetSure ITM DC UPS must be fully installed and commissioned before startup.
Procedure
1.
Open the front door on each DC UPS module.
2.
Apply AC input power to each DC UPS module by closing the external AC disconnect(s) or 
protective device(s) that supplies power to each DC UPS module. If the dual AC input feed option 
is furnished, there will be two (2) devices per DC UPS module.
3.
On each DC UPS module, close the main AC input circuit breaker. If the dual AC input feed 
option is furnished, a safety latch is provided on the circuit breakers to prevent both circuit 
breakers from being placed in the ON position. Slide the latch over to allow the desired circuit 
breaker to be turned ON.
4.
On each DC UPS module, close all PCU AC input circuit breakers. Note that each circuit breaker 
feeds two (2) PCUs.
5.
In the Primary DC UPS module, once the ACU+ Controller is powered on, a starting... screen 
appears followed by a language screen.
Press “
” or “
” to select the desired language. Press ENT to confirm the selection. If no key is 
pressed within 30 seconds, the ACU+ Controller automatically selects the displayed language.
Refer to the NetSure ITM Operation Manual (Section 6047) for ACU+ Controller local menu 
operating instructions.
Once initialized, the ACU+ Main Screen displays.
6.
With an external meter, measure battery voltage.
7.
Adjust the system’s float voltage to within approximately 0.5V of battery voltage.
8.
In each DC UPS module, install the three battery disconnect fuses.
9.
Adjust the system’s float voltage to 54.5Vdc.
10. In each DC UPS module, place each distribution circuit breaker to the ON position or install all 
distribution fuses.
11. In the Primary DC UPS module, verify that there are no alarms present on the ACU+ local 
display.
6.3.2
Setting Common Controller Parameters
Navigate through the controller menus and submenus to set common controller parameters (time, 
date, IP address, etc.). Refer to Section 3.5 of the NetSure ITM Operation Manual (Section 6047) for 
common tasks performed locally.
English
0 9:2 0 :2 0
F lo a t
5 3 .4 V     40 4 A
Auto 
N o Alarm
M A IN  M E N U
S ta tus
Settings
Energy Saving
Manual
CustomizeMenu
E N T
E S C
Main Screen
Main Menu
Press      or    
to browse through
MAIN MENU.
Press ENT to
enter Sub-Menu.