Pins 5 & 6 - Any-Mode Shutdown 
1. Pin 6 of the 9-pin communication connector is used for “Any-Mode Shut-
down” of the UPS output. This control input may be used in special applica-
tions to disable the UPS output power—both Inverter and Bypass.
2. The Options tab allows the behavior of the Any-Mode Shutdown feature to 
be modified. When the program opens, or the REFRESH button is pressed, 
the UPS setting is read by the configuration program and displayed.
Auto-Enable Output
Pin 6 Logic
If version 1.6 (or later) is used with an earlier Liebert GXT2U model (with an 
earlier UPS firmware version), the Any-Mode Shutdown features cannot be 
changed.
If the configuration program is used with an earlier UPS model (with an 
earlier UPS firmware version) that does not support the modification of these 
settings, the Options tab will display a reminder of the factory default 
settings. These cannot be changed.
!
WARNING
Note that when this option is selected and the UPS output is 
disabled using Pin 6, the UPS output can turn on automatically 
and without warning if the Pin 6 connection is changed.
!
WARNING
DO NOT CHANGE THIS OPTION from the factory default 
setting unless you are ready to install a normally-closed 
connection between Pins 5 & 6. This connection must be 
maintained to use the UPS or to use the configuration program 
again, including the ability to change the UPS setting back to the 
default setting using the configuration program via a serial 
communication link.