22      Chapter 3  Electrical Installation 
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA    User Manual 
Table 3-5    Description of dry contact output port   
Position  
Name  
Description  
J13.2   
BFP_O   
Bypass feedback protection relay (NO)   
J13.3   
BFP_S   
Bypass feedback protection relay center   
J13.4   
BFP_C   
Bypass feedback protection relay (NC)   
J21.2   
INV_O   
On inverter dry contact relay (NO) 
J21.3   
INV_S   
On inverter dry contact relay center 
J21.4   
INV_C   
On inverter dry contact relay (NC) 
J25.2   
ACF_O   
Main input voltage or frequency fault relay (NO)   
J25.3   
ACF_S   
Main input voltage or frequency fault relay center   
J25.4   
ACF_C   
Main input voltage or frequency fault relay (NC)   
 
  Note 
All auxiliary cables must be double insulated. Wire should be 0.5~1.5mm
2
 stranded. 
 
EPO input port (X2) 
The UPS has an Emergency Power Off (EPO) function that operates by a button on the UPS door or by a remote 
contact provided by the user.     
The X2 slot, shown in Figure 3-7, is the remote EPO input port, which is described in Table 3-6.   
 
Figure 3-7    EPO input port 
Table 3-6    Description of EPO input port   
Position  
Name  
Description  
J28.1   
EPO_NC   
EPO activated when opened to J28.2   
J28.2   
EPO_NC   
EPO activated when opened to J28.1   
J28.3   
EPO_NO   
EPO activated when shorted to J28.4   
J28.4   
EPO_NO   
EPO activated when shorted to J28.3   
 
The remote EPO facility is connected to the normally open or normally closed remote stop switch between these two 
terminals using shielded cable. If this function is not used, terminals J28: 3&4 must be opened and J28: 1&2 must be 
closed.  
  Note 
The emergency stop action within the UPS shuts down the rectifier, inverter and static bypass. It does not internally disconnect the 
input power supply. To disconnect ALL power to the UPS, open the upstream feeder breaker(s) when the remote EPO is 
activated. 
Normally closed EPO–J28: 1, 2, these terminals are supplied factory-linked on the monitor board. 
 
Auxiliary DC power output port (X5) 
The auxiliary DC power output port X5 provides auxiliary DC power for optional SNMP card. The voltage is between 
9V to 12V. The maximum current is 500mA.   
Communication ports 
The communication ports include the serial ports RS232-1 and RS232-2, Intellislot intelligent communication ports. 
1. Serial ports RS232-1 and RS232-2   
RS232-1 provides serial data and is intended for direct use with Emerson UPSitePlus
TM
 UPS monitoring software.   
RS232-2 provides serial data and is intended for use by authorized commissioning and service personnel.