Emerson AXP1406 Manuel D’Utilisation

Page de 148
Shelf FRU Info (Emerson OEM)
OEM Sensors
AXP1406/AXP1600 Subsystem IPMI Programmer’s Reference (6806800B66C)
139
   
                      Bit 5 (CRC)
                      Bit 6 (Watchdog)
                      Bit 7 (RTC)
3.1.4
Shelf FRU Info (Emerson OEM)
This sensor reports the validity of the Shelf FRU Information. This sensor is available on each 
physical ShMM controller. The check it performs is basic checksum and length checks based 
on information of previous sections of the FRU area; and key bytes that are expected to have 
certain values.
z
Sensor Reading - 0x00 (meaningless since discrete sensor reading)
z
Current State Mask - 0x01 Shelf FRU Info not found (Disabled)
                               
0x02 Shelf FRU Info found (Enabled)
z
Events - Events are generated when the state of the FRU Info found state changes.
Event Data Byte 1 = 0x01 Shelf FRU Info not found (Disabled)
                                 
0x02 Shelf FRU Info found (Enabled)
Event Data Byte 2 = 0xFF (Unspecified)
Event Data Byte 3 = 0xFF (Unspecified)
3.1.5
FT -48 V Fuse (Emerson OEM)
This sensor reads the System Status Register of the respective Fan Tray and verifies if the bit 
for 48 V input power OK is set.   The 48 V input power ok bit is set if all input fuses are intact.
z
Sensor Reading - 0x00 (NULL Discrete sensor reading)
z
Current State Mask - 0x01 (State Deasserted, all input fuses are intact)
                                     0x02 (State Asserted, not all input fuses are intact)
z
Events - No events are generated by this sensor.