Emerson SERIES 600T Manuel D’Utilisation

Page de 168
UPS Interconnection Kits
91
Appendix A.3.2 Status/Control Connections - Liebert Npower UPS Interconnection Kit
The status/control interface is the Liebert Npower Battery Information Board (BIB). The connection 
cally operated circuit breaker Liebert Npower unitsRefer to this drawing to ensure that the 
proper connections are performed. In case multiple Liebert FS units are connected to the same UPS 
lel for capacity to perform the Status/Control connections between each Liebert FS.
This interconnection kit includes Status/Control Connections that enable transfer of signals between 
the Liebert FS system(s) and the UPS system such as:
• Circuit breaker status (closed/open); and
• Undervoltage relay coil excitation voltage.
The recommended gauge for status/control connection wires is 16 AWG - 600VDC (1.3mm
2
 wire sec-
tion). Wire size and installation must comply with all applicable local, regional and national regula-
tions (e.g., National Electric Code for USA).
Appendix A.3.3 UPS Configuration - Liebert FS and Liebert Npower
To optimize the integration between the Liebert Npower UPS system and the Liebert FS, some 
parameters must be checked on the UPS system:
• The UPS rectifier walk-in time must be set at a value as low as possible. Contact your Liebert rep-
resentative if your unit has received the upgraded board that permits the setting of “rectifier 
walk-in time” lower than standard.
• Ensure that the “auto battery self test” has either been disabled or upgraded to accommodate 
Liebert FS integration.
Appendix A.3.4 Liebert FS Configuration - Single Liebert FS Unit
The following Software Control Parameters must be set when the Liebert FS is connected to the 
DC bus of the Liebert Npower UPS system.
NOTE
The Software Control Parameter values specified below are recommended. These values may 
require adjustments due to the battery type. These must be used unless otherwise specified by 
the Liebert-certified service technician at initial system startup. Instructions to set these 
parameters on the Liebert FS are in 6.5.3 - Control Parameters Setup at Initial System 
Table 23
Liebert FS Software Control Parameters
Liebert FS Software
Control Parameter
Setting
Charge Voltage 
520VDC
Regulation Voltage 
510VDC
Vreg Delta
0VDC
Maximum Charge Current
Charge Amps/Volts 
Table 24
Liebert FS Software Control Parameters varying with UPS size
UPS Output Rating (kVA)
30
40
50
65
80
100
130
Liebert FS Maximum Charge Current (A)
11
15
19
25
31
38
50
Liebert FS Charge Amps/Volts (A/V)
0.8
1.0
1.3
1.7
2.1
2.6
3.4