Emerson SERIES 600T Manuel D’Utilisation

Page de 168
Versatile Interface Board
111
Appendix C.2.5 VIB Connections
The VIB is supplied with removable screw-terminal connectors to allow for easy integration 
Figure 119. The user must supply the wire as specified below to make the connections to the VIB 
connectors.
• Wire gauge: 12-24 AWG
• Stripped length: 0.125" - 0.250"
• Tightening torque: 4.4 inch-pounds (maximum)
Figure 119 VIB screw terminal connections
Appendix C.3 VIB Operation
Upon Initial System Startup of the Liebert FS by a Liebert-certified service technician, your VIB will 
be operational. There is nothing to turn on or configure. Make sure that all external connections to 
the VIB are made with the Liebert FS power off. Making connections while power is applied may have 
undesirable effects and may damage the equipment.
Appendix C.3.1 VIB Operational States
The operational status of the VIB is indicated on the main screen of the Display Panel. There are 
three possible states: “Enabled”, “Disabled” and “Not Available”. They are indicated on the Display 
Panel by “1,” “0” or “NA,” respectively.
“Enabled” State
If the VIB is detected when the system is powered-up or rebooted, it will automatically be enabled. If 
for any reason the VIB has been disabled, it can be re-enabled by pressing F6 (Setup Parameters), 
then F3 (UIB Enable). While the VIB is enabled, the “Start,” “Stop” and “Clear Fault” buttons will not 
be visible on the Display Panel. To control the Liebert FS from the Display Panel, the VIB must first 
be disabled.
“Disabled” State
If the VIB is not detected when the system is powered-up or rebooted, it will automatically be dis-
abled. At any time during operation the VIB can be disabled by pressing F6 (Setup Parameters), then 
F3 (UIB Disable). When the VIB is disabled, the inputs are ignored and all outputs are turned off. 
Before disabling the VIB, consider how disabling the board will affect other system components.
“Not Available” State
The Liebert FS continually monitors the status of the VIB to verify that it is operating correctly. If the 
response from the VIB is not what is expected by the Liebert FS, “WARNING” will be displayed on 
the front panel.