Installation Drawings
138
Figure 146 Wiring specifications, Liebert FS and Liebert Npower
Wire
No.
Terminal Designation
Signal
Name
Maximum
Voltage
Maximum
Current
Color
Wire Size
& Type
Maximum
Length Remarks
From
To
Liebert N-Power UPS - Cable Group # 17 (Flywheel CB IFM) From TB69 in UPS Module to TB1 on Liebert FS Module
101
TB69-1
TB1-1
Trip Signal (+)
+24 VDC
100mA
1/C #16 (2.5 mm
2
)
Stranded
1/C #16 (2.5 mm
2
)
Stranded
500 ft
(150m)
102
TB69-2
TB1-2
Trip Signal (-)
-24 VDC
100mA
103
TB69-3
TB1-3
Motor Op Relay
24 VDC
100mA 
104
TB69-4
TB1-4
Motor Op On
24 VDC
100mA 
105
TB69-5
TB1-5
Motor Op Off
24 VDC
100mA
106
TB69-6
TB1-6
Aux N.O.
24 VDC
100mA
107
TB69-7
TB1-7
Aux Comm
24 VDC
100mA 
108
TB69-8
TB1-8
Aux N.C.
24 VDC
100mA
109
TB69-9
TB1-9
Comm
24 VDC
100mA
110
TB69-10
TB1-10
Battery Sense (+) +24 VDC
100mA
112
TB69-12
TB1-11
Battery Sense (-) -24 VDC
100mA
Liebert N-Power UPS - Cable Group # 18 (Flywheel CB IFM) from TB73 in UPS Module to TB6 on Liebert FS Module
Line
TB73-1
TB6-1
Motor Op Pwr
120 VAC
100mA
500 FT
(150m)
Neutral
TB73-2
TB6-2
Motor Op Neutral
N
100mA
Liebert N-Power UPS - Cable Group # 19 (Flywheel CB IFM) From TB70 in UPS Module to TB7 on Liebert FS Module
113
TB70-1
TB7-1
Temp Sensor
24 VDC
100mA
1/C #16 (2.5 mm
2
)
Stranded
500 ft
(150m)
114
TB70-2
TB7-2
Sensor Return
24 VDC
100mA
Liebert N-Power UPS - Cable Group # 116 Flywheel Aux Power, Customer Provided to Liebert FS TB1 on Fused 
Disconnect
Output
A PHS
FBO
TB1-1
Line
120VAC
3.5A
1/C #16 (2.5 mm
2
)
Stranded
500 ft
(150m)
UPS-
Protected
Auxiliary
Control
Power
Output
Net
FBO
TB1-2
Neutral
120VAC
3.5A 
Gnd
FBO
TB1-3
GND
120VAC
3.5A
1. Each cable group must be run in a separate grounded rigid metal conduit to prevent control signal interference.
2. Refer to UPS module/Liebert FS control connection diagram for location of wiring connections.
3. All external wires furnished by others.
4. N.O. = Normally Open; N.C. = Normally Closed; Comm = common; F.B.O. = Furnished By Others, GND = ground
5. All wiring must be in accordance with national and local electrical codes.
Dwg. No. Control_WL_NPower_Liebert-FS Rev. 1