Emerson SERIES 600T Manuel D’Utilisation

Page de 168
General System Information
9
Figure 6
Integrating a single Liebert FS unit into a UPS system
Several Liebert FS units can be put in parallel to achieve higher power output and higher ride-
through duration (see Figure 7). One or more Liebert FS units may also be connected in parallel with 
a UPS battery plant (valve- regulated or wet cells) to provide an overall incremental reliability and 
life improvement for the DC battery plant. In this situation, the Liebert FS unit would be connected 
in parallel with the battery plant (through its own disconnect device) to the UPS DC Bus.
Figure 7
Integrating multiple Liebert FS units into a UPS system
EMERSON
Network Power
Lieber t
CRITICAL 
AC LOADS
UPS
Output 
Breaker
UPS
DC
Bus
Liebert FS
Static
Switch
UPS
Rectifier
UPS
Input
Breaker
Feeder 
Breaker
Bypass
Utility
GRID
Bypass
Breaker
UPS Block Diagram
EMERSON
Network Power
Liebert
EMERSON
Network Power
Liebert
EMERSON
Network Power
Liebert
Liebert FS
Unit #1
Liebert FS
Unit #2
Liebert FS
Unit #N
UPS
Output 
Breaker
UPS 
Input
Breaker
Feeder 
Breaker
Bypass
Utility
GRID
CRITICAL 
AC LOADS
UPS
DC Bus
Static
Switch
UPS Block Diagram
UPS
Inverter
UPS
Rectifier
Bypass Breaker