"DC" Parameter Settings: 
 
Shunt Current: Enter the load shunt
’s current rating. 
 
Shunt Voltage: Enter the load shunt
’s voltage rating. 
 
LoadShuntExist: Select whether a load shunt exists or not. 
LVD 
LVD Group Menu 
Menu Navigation: Main Menu / Settings / LVD / LVD Group 
Note: For WEB Interface; menu items are found under Device Information / LVD Group / Settings 
Tab. 
Note:  This feature requires a BTRM sensor. The BTRM sensor is the sensor which is used for the 
High Temperature Disconnect (HTD) Feature. 
"LVD Group" Parameter Settings: 
 
HTD Recon Point: Sets temperature at which a reconnect will occur following a High 
Temperature Disconnect. 
 
HTD Point: Sets high temperature limit at which LVD1 and/or LVD2 contactors will open 
(disconnect) if the HTD1 and/or HTD2 features are enabled. If this temperature is reached, 
a disconnect occurs regardless of voltage. 
LVD Unit Menu 
Menu Navigation: Main Menu / Settings / LVD / LVD Unit 
Note: For WEB Interface; menu items are found under Device Information / LVD Group / LVD Unit 
/ Settings Tab. 
"LVD Unit" Parameter Settings: 
 
LVD1: Enables or disables LVD1. 
 
LVD1 Mode: Sets LVD1 to disconnect on a voltage or time setpoint. 
 
LVD1 Volt: LVD1 low voltage disconnect setting (when LVD set for voltage). 
 
LVD1 Recon Volt: LVD1 reconnect setting (when LVD set for voltage). 
 
LVD1 ReconDelay: Delay time period until LVD1 reconnects once voltage recovers 
(when LVD set for voltage). 
 
LVD1 Time: The time period before LVD1 disconnection once an AC fail condition 
occurs (when LVD set for time). 
 
LVD1 Dependency: Select if LVD1 can disconnect only if LVD2 has disconnected, or 
none. 
 
LVD2: Enables or disables LVD2. 
 
LVD2 Mode: Sets LVD2 to disconnect on a voltage or time setpoint. 
 
LVD2 Volt: LVD2 low voltage disconnect setting (when LVD set for voltage). 
 
LVD2 Recon Volt: LVD2 reconnect setting (when LVD set for voltage). 
 
LVD2 ReconDelay: Delay time period until LVD2 reconnects once voltage recovers 
(when LVD set for voltage). 
 
LVD2 Time: The time period before LVD2 disconnection once an AC fail condition 
occurs (when LVD set for time). 
 
LVD2 Dependency: Select if LVD2 can disconnect only if LVD1 has disconnected, or 
none.