Clr MtncRunTime*: The only selection for "Clear Maintenance Run Time" is Yes. Once 
Yes is selected and confirmed, the Power System’s Maintenance Run Time log is cleared. 
Rectifier 
All Rect Ctrl Menu 
Menu Navigation: Main Menu / Manual / Rectifier / All Rect Ctrl 
Note: For WEB Interface; menu items are found under Device Information / Rectifier Group / select 
the Control tab. 
"All Rect Ctrl" Parameter Settings: 
 
Rectifier Trim: Temporarily sets the output voltage for all rectifiers. Voltage can be 
increased or decreased from the existing Float Charge or Equalize Charge setting, 
depending which mode the Controller was in when set to "Manual". Setting reverts to 
original when Controller is returned to the Auto mode. 
 
DC On/Off Ctrl: Temporarily turns the DC output on or off for all rectifiers. Setting returns 
to original when Controller is returned to the Auto mode. 
 
AC On/Off Ctrl: Temporarily turns the AC input on or off for all rectifiers. Setting returns to 
original when Controller is returned to the Auto mode. 
 
Rect LED Ctrl: 
Temporarily sets whether or not a rectifier’s local power indicator blinks 
when the Controller is communicating with the rectifier. Setting returns to original when 
Controller is returned to the Auto mode. 
 
Fan Speed Ctrl: Temporarily sets the fan speed for all rectifiers. Setting returns to original 
when Controller is returned to the Auto mode. 
 
Confirm ID/PH*: Confirms the position and input phase for all rectifiers. 
 
Clear Rect Lost*: Clears a rectifier lost alarm. 
 
Reset Cycle Alm*: Clears a rectifier oscillator alarm. 
 
Clear Comm Fail*: Clears a rectifier communication fail alarm. 
Rect #1 Menu 
Menu Navigation: Main Menu / Manual / Rectifier / Rect #1 
Note: For WEB Interface; menu items are found under Device Information / Rectifier Group / 
Rectifier #1 / select the Control tab. 
"Rect #1" Parameter Settings: 
 
DC On/Off Ctrl: 
Temporarily turns the rectifier’s DC output on or off. Setting returns to 
original when Controller is returned to the Auto mode. 
 
AC On/Off Ctrl: 
Temporarily turns the rectifier’s AC input on or off. Setting returns to 
original when Controller is returned to the Auto mode. 
 
LED Control: 
Temporarily sets whether or not the rectifier’s local power indicator blinks 
when the Controller is communicating with the rectifier. Setting returns to original when 
Controller is returned to the Auto mode. 
 
Rectifier Reset*: Resets the rectifier. 
Batt Group 
Batt Group Menu 
Menu Navigation: Main Menu / Manual / Batt Group 
Note: For WEB Interface; menu items are found under Device Information / Battery Group / select 
the Control tab.