Rectifier Expansion 
Rectifier Expansion Menu 
Up to four (4) ACU+ Controllers can be connected together when a power system requires a 
greater number of rectifiers than can be controlled by a single ACU+ Controller. One (1) Controller 
is designated as the primary Controller, the others as secondary Controllers. The rectifiers 
controlled by the secondary Controllers are designated as RectifierGroup 2 though 4 in the menus. 
Primary/Secondary Procedure: 
Note:  Changing the Rectifier Expansion setting may take more than 3 minutes for the ACU+ to 
configure the feature. 
1)  Connect the ACU+ Controllers in the multiple bays via the RS485 interface. 
2)  Set one of the ACU+ Controllers as the Primary Controller (see below). 
3)  Set all other ACU+ Controllers as Secondary Controllers (see below). 
4)  Set the Address of the ACU+ Controllers set as Secondary Controllers to 201, 202, or 203 
(see below). Note that each Secondary Controller must be set to a different address. 
Menu Navigation: Main Menu / Quick Setting / Rectifier Expansion  
Note: For WEB Interface; menu items are found under Quick Settings / Rectifier Expansion. 
"Rectifier Expansion" Parameter Settings: 
 
Rect Expansion 
 
Inactive: Select this option if this is the only ACU+ Controller in the power system. 
 
Primary: Select this option if the power system consists of multiple bays with multiple 
ACU+ Controllers, and this ACU+ Controller is to be the Primary Controller. Note that 
only one (1) ACU+ Controller can be set as the Primary Controller. 
 
Secondary: Select this option if the power system consists of multiple bays with 
multiple ACU+ Controllers, and this ACU+ Controller is to be a Secondary Controller. 
 
Address (Slave): Sets the address of an ACU+ Controller set as a Secondary Controller.