Battery Discharge Test and Battery Test Logs 
The ACU+ Controller can perform battery discharge tests to check the condition of the battery. 
There are (3) types of battery discharge tests. 
 
Short Time Test 
 
Time Test 
 
Stable Current Test 
A User can manually start a battery discharge test or program the ACU+ Controller to automatically start 
battery discharge tests at scheduled intervals (cyclic battery tests). During a battery discharge test, the 
ACU+ Controller controls the rectifiers output to place the entire load or partial load on the batteries. The 
ACU+ Controller monitors the discharge of the battery and saves the results in a battery test log.
 
Functional Description: For manual battery discharge tests as well as for cyclic battery discharge tests, 
the following parameters must be set: End Voltage, Test Time, and Battery Capacity Discharge Limit. See 
Figure 4. 
Battery Discharge Test Sequence: 
 
In time test modes, the output voltage of the rectifiers is reduced so that only the batteries power the 
load. If the batteries fail, the rectifiers power the load. 
 
In stable current test mode, the output voltage of the rectifiers is reduced so that the batteries supply 
the preset test current to the load. 
 
The battery test continues until one of the following occurs: 
  The preset test time, see Figure 4, expires. The battery has passed the test. 
  The battery voltage drops below the preset end voltage level (V
end
) (Figure 4). The battery has not 
passed the test and the test is interrupted. A battery test alarm is activated. 
  The battery capacity drops below the preset test end battery capacity. The battery has not passed 
the test and the test is interrupted. A battery test alarm is activated. 
 
After the battery discharge test, the output voltage of the rectifiers increase so that the rectifiers supply 
the system and charge the batteries. 
 
Figure 4 
Battery Test Diagram